Installing the S7-400
2-28
Automation System S7-400 Hardware and Installation
A5E00850741-01
Example of selecting the cabinet type
The example below clarifies the maximum permissible ambient temperature at a
particular power loss for various cabinet types.
Equipment suitable for installation in a cabinet:
1 central rack
150 W
2 expansion racks, 150 Watts each
300 W
1 load current power supply under full load
200 W
Accumulated power loss
650 W
Permissible ambient temperatures at an accumulated power loss as shown in
Figure 2-2:
Type of Cabinet
Max. Permissible Ambient
Temperature
Closed, with natural convection and forced circulation
(Curve 3)
(no operation possible)
Open, with through-ventilation (Curve 2)
approx. 38
°
C
Closed, with heat exchanger (Curve 1)
approx. 45
°
C
Cabinet dimensions
Vital dimensional design factors for an S7-400 cabinet
•
Space requirement of the racks
•
Minimum clearance between racks and cabinet walls
•
Minimum clearance between racks
•
Space requirement of cable ducts or fan subassemblies
•
Locations of rails
Содержание Simatic S7-400
Страница 6: ...Preface vi Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 52: ...Installing the S7 400 2 36 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 60: ...Addressing the S7 400 3 8 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 128: ...Networking 5 30 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 148: ...Commissioning 6 20 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 228: ...Index Index 4 Automation System S7 400 Hardware and Installation A5E00850741 01 ...