Installing the S7-400
2-10
Automation System S7-400 Hardware and Installation
A5E00850741-01
2.5
Mounting and Grounding the Racks
Important Notes on Installation
The S7-400 racks are designed for wall mounting, mounting on rails, and for
installation in frames and cabinets. Their mounting dimensions are compliant with
DIN 41 494.
According to the UL/CSA and the EU Directive 73/23/EEC (low-voltage directive),
installation in a cabinet, a casing, or a closed operations room is necessary in order
to fulfil the requirements for electrical safety (see
Reference Manual
, Chapter 1).
Step 1: Retaining Distances Between Devices
You must observe the minimum distances between the rack and neighboring
devices. You need these minimum clearances during installation and operation.
•
For fitting and removing modules
•
For fitting and disconnecting the module front connectors
•
To ensure the air flow required for cooling the modules during operation
The following figure shows the minimum space you must provide for a rack.
20 mm
20 mm
40 mm
22 mm
352 mm
Mounting depth, fitted: max. 237 mm
40 mm facilitates the mounting of a fan subassembly
*
*
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18
523 mm (18 slots)
298 mm (9 slots)
173 mm (4 slots)
Содержание Simatic S7-400
Страница 6: ...Preface vi Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 52: ...Installing the S7 400 2 36 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 60: ...Addressing the S7 400 3 8 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 128: ...Networking 5 30 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 148: ...Commissioning 6 20 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 228: ...Index Index 4 Automation System S7 400 Hardware and Installation A5E00850741 01 ...