The EMC measures are applied to all three components to prevent malfunctions due to
interference. When setting up a plant, the manufacturer must take all possible measures to
prevent the occurrence of interference sources:
• Only devices fulfilling limit class A of VDE 0871 may be used in a plant.
• Interference suppression measures must be introduced on all interference-emitting devices.
This includes all coils and windings.
• The design of the system must be such that mutual interference between individual
components is precluded or kept as small as possible.
Information and tips for plant design are given in the following sections.
Interference sources
To achieve a high level of electromagnetic compatibility and thus a very low level of interference
in a plant, it is necessary to recognize the most frequent interference sources. These must then
be eliminated by appropriate measures.
Table 4-75
Interference sources: Origin and effect
Interference source
Interference results from
Effect on the interference sink
Conveyor technology and
transport units from a materi‐
al that is conducive to electro‐
static charging
Static charge
Electrical discharge currents, electrical
field
Operator
Contactor,
electronic valves
Contacts
System disturbances
Coils
Magnetic field
Electric motor
Collector
Electrical field
Winding
Magnetic field
Electric welding device
Contacts
Electrical field
Transformer
Magnetic field, system disturbance,
transient currents
Power supply unit, switched-
mode
Circuit
Electrical and magnetic field, system
disturbance
High-frequency appliances
Circuit
Electromagnetic field
Transmitter
(e.g. professional mobile ra‐
dio)
Antenna
Electromagnetic field
Ground or reference potential
difference
Voltage difference
Transient currents
Power cables
Current flow
Electrical and magnetic field, system
disturbance
High-voltage cable
Voltage difference
Electrical field
Planning the RF300 system
4.6 Guidelines for electromagnetic compatibility (EMC)
SIMATIC RF300
112
System Manual, 02/2021, C79000-G8976-C345-09
Содержание SIMATIC RF300
Страница 14: ...Table of contents SIMATIC RF300 14 System Manual 02 2021 C79000 G8976 C345 09 ...
Страница 18: ...Introduction 1 1 Preface SIMATIC RF300 18 System Manual 02 2021 C79000 G8976 C345 09 ...
Страница 22: ...Safety information 2 1 Security information SIMATIC RF300 22 System Manual 02 2021 C79000 G8976 C345 09 ...
Страница 208: ...Readers 5 6 SIMATIC RF382R with Scanmode 1st generation SIMATIC RF300 208 System Manual 02 2021 C79000 G8976 C345 09 ...
Страница 258: ...Antennas 6 10 ANT 30 stainless steel variant SIMATIC RF300 258 System Manual 02 2021 C79000 G8976 C345 09 ...
Страница 474: ...Service Support SIMATIC RF300 474 System Manual 02 2021 C79000 G8976 C345 09 ...