Combination options of the power supply PS with TM-PS-A and TM‑PS‑B UC or TM‑PS‑A UC and TM-
PS-B
TM-PS-A
TM-PS-B UC
PS 24 VDC*
PS 120/230 VAC**
TM-PS-A UC
TM-PS-B
PS 120/230 VAC**
PS 24 VDC*
* Product version 5 and higher
** Maximum output current, refer to technical specifications in the section
Power Supply PS 120/230 VAC
Installation and Wiring
1. Begin the installation with the TM-PS-A/ TM-PS-A UC.
2. Install the TM-PS-B/ TM-PS-B UC to the right of the TM-PS-A/ TM-PS-A UC.
3. Now complete the ET 200iSP configuration.
4. Connect a separate power supply to each TM.
5. Finally, fit the TMs with Power Supply PS 1 and PS 2.
7036$7036$8&
7036%7036%8&
36 36
$&
'&
$&
'&
Figure 3-5
Redundancy of the Power Supply (example)
Parameter Assignment
Only those parameters that are relevant for the redundancy of the power supply are explained
below. These are part of the parameters of the IM 152 interface module.
Table 3-7
Parameters for redundancy of the Power Supply PS
Parameters
Setting
Description
Self-diagnostics
enabled
---
Redundant Power Sup‐
ply diagnostics
Redundant Power Supply
Diagnostics in the event of failure of
Power Supply PS 1 or PS 2
Configuration options
3.11 Redundancy of the Power Supply
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
61
Содержание SIMATIC ET 200iSP
Страница 82: ...Configuration options 3 18 Redundancy with IM 152 ET 200iSP 82 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 184: ...Commissioning and Diagnostics 6 8 Diagnostics with STEP 7 ET 200iSP 184 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 194: ...Maintenance 7 7 Reading service data ET 200iSP 194 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 220: ...Terminal modules 9 6 Terminal module TM RM RM ET 200iSP 220 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 372: ...Glossary ET 200iSP 372 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 384: ...Index ET 200iSP 384 Operating Instructions 11 2017 A5E00247483 07 ...