input signal is fixed at "zero" and the value status is "invalid" because this channel is only used
for a validity check of the sensor.
Note the following points when carrying out a diagnosis for a changeover contact sensor type:
● If there is already an error on the normally open contact channel (a wire break, for example),
the module no longer performs diagnostics for changeover contact errors. The diagnostics
for changeover contact errors continues on the second channel.
● You will find additional points to note in the following table:
Table 12-7
Diagnosis for changeover contacts
Changeover contact
A negative check means...
Changeover contact as NA‐
MUR
● Short-circuit or
● Wirebreak
Additionally:
Changeover contact or ex‐
ternal fault (in case of DP
diagnostics)
Closed changeover contact
● Sensor defective or short-circuit
No distinction can be made here between a defective-sensor
and short circuit
Open changeover contact
Caution: no differentiation possible between
● signal "0" and wire break
● Signal "1" and short circuit
12.2
Digital electronics module 4 DO
Order number
Type
Order number
4 DO DC23.1V/20mA SHUT DOWN "H"
6ES7132-7RD01-0AB0
4 DO DC17.4V/27mA SHUT DOWN "H"
6ES7132-7RD11-0AB0
4 DO DC17.4V/40mA SHUT DOWN "H"
6ES7132-7RD21-0AB0
4 DO DC23.1V/20mA SHUT DOWN "L"
6ES7132-7GD00-0AB0
4 DO DC17.4V/27mA SHUT DOWN "L"
6ES7132-7GD10-0AB0
4 DO DC17.4V/40mA SHUT DOWN "L"
6ES7132-7GD20-0AB0
Properties
● 3 variants of SHUT DOWN "H" output modules
● 3 variants of SHUT DOWN "L" output modules
● 4 outputs per module
● Nominal load voltage 23.1 V DC or 17.4 V DC
● Outputs suitable for EEx i solenoid valves, DC current relay and actuators
Digital electronic modules
12.2 Digital electronics module 4 DO
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
243
Содержание SIMATIC ET 200iSP
Страница 82: ...Configuration options 3 18 Redundancy with IM 152 ET 200iSP 82 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 184: ...Commissioning and Diagnostics 6 8 Diagnostics with STEP 7 ET 200iSP 184 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 194: ...Maintenance 7 7 Reading service data ET 200iSP 194 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 220: ...Terminal modules 9 6 Terminal module TM RM RM ET 200iSP 220 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 372: ...Glossary ET 200iSP 372 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 384: ...Index ET 200iSP 384 Operating Instructions 11 2017 A5E00247483 07 ...