Note
Control response
A control response is implemented for assigning parameters in the electronic modules of the
ET 200iSP.
If the electronic module receives a faulty parameter, this is rejected. The electronic then
continues to operate with its already valid parameters (the default parameters from the initial
parameter assignment). No "parameter error" diagnostic messsage is output.
The update interrupt function can be used to check the changed parameters of the electronic
module. See section "Interrupts (Page 171)".
No update interrupt is generated in the case of faulty parameters.
6.8.12
H-Status (only with the S7-400H and standard redundancy)
H-status
The IM 152 supplies the H-status only if it is running on an S7-400H DP master or is operated
redundantly according to the standard.
In the structure of the slave diagnostics, the H-status is represented by an additional block,
typically following the manufacturer's ID.
Commissioning and Diagnostics
6.8 Diagnostics with STEP 7
ET 200iSP
170
Operating Instructions, 11/2017, A5E00247483-07
Содержание SIMATIC ET 200iSP
Страница 82: ...Configuration options 3 18 Redundancy with IM 152 ET 200iSP 82 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 184: ...Commissioning and Diagnostics 6 8 Diagnostics with STEP 7 ET 200iSP 184 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 194: ...Maintenance 7 7 Reading service data ET 200iSP 194 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 220: ...Terminal modules 9 6 Terminal module TM RM RM ET 200iSP 220 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 372: ...Glossary ET 200iSP 372 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 384: ...Index ET 200iSP 384 Operating Instructions 11 2017 A5E00247483 07 ...