Installing terminal module TM-PS-A/ TM-PS-A UC
1. Fit the terminal module onto the rail.
2. Push in the terminal module at the bottom until you can hear the catch lock.
3. Screw the terminal module to the mounting rail (2 screws - torque 0.8 to 1.1 Nm). Use a
screwdriver with a 4.5 mm wide blade.
Note
To avoid the ET 200iSP slipping to the side, the terminal module must be secured
mechanically (see point 3). The 2 fastening screws are located on the front at the bottom
of the terminal module.
An inserted Power Supply PS can only be uninstalled if both fastening screws are tightened
on the terminal module.
①
Catch
Figure 4-6
Installing terminal module TM-PS-A/ TM-PS-A UC
Installing terminal module TM-PS-B/ TM-PS-B UC (second Power Supply PS)
1. Hang terminal module TM-PS-B/ TM-PS-B UC to the right of the TM-PS-A/ TM-PS-A UC
on the mounting rail.
2. Swivel the TM-PS-B/ TM-PS-B UC back until you can hear the catch lock.
Installing
4.3 Installing the terminal module for power supply PS
ET 200iSP
94
Operating Instructions, 11/2017, A5E00247483-07
Содержание SIMATIC ET 200iSP
Страница 82: ...Configuration options 3 18 Redundancy with IM 152 ET 200iSP 82 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 184: ...Commissioning and Diagnostics 6 8 Diagnostics with STEP 7 ET 200iSP 184 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 194: ...Maintenance 7 7 Reading service data ET 200iSP 194 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 220: ...Terminal modules 9 6 Terminal module TM RM RM ET 200iSP 220 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 372: ...Glossary ET 200iSP 372 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 384: ...Index ET 200iSP 384 Operating Instructions 11 2017 A5E00247483 07 ...