STEP 7 User Program
STL
Explanation
Call SFC 13
REQ :=TRUE
LADDR :=W#16#3FE
RET_VAL :=MW 0
RECORD :=P#DB82.DBX 0.0 BYTE 96
BUSY :=M2.0
Read request
Diagnostics address of the ET 200iSP
RET_VAL from SFC 13
Data compartment for the diagnostics in DB 82
Read process runs over several OB1 cycles
6.8.3
Diagnostic messages of the electronic modules
Introduction
You can set parameters for the diagnostic messages of the following modules:
● Digital input modules
● Digital output modules
● Analog input modules
● Analog output modules
Digital input modules
Table 6-10
Digital input modules
Diagnostic message
Applicability
Can be set
Short-circuit
Channel
Yes
Wire break
Channel
Yes
Error
Module
No
External fault
Channel
No
Digital output modules
Table 6-11
Digital output modules
Diagnostic message
Applicability
Can be set
Short-circuit
Channel
Yes
Wire break
Channel
Yes
Error
Module
No
Actuator disconnection
Channel
Yes
1
1
Enabling the actuator disconnection by means of the group diagnostics parameter
Commissioning and Diagnostics
6.8 Diagnostics with STEP 7
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
155
Содержание SIMATIC ET 200iSP
Страница 82: ...Configuration options 3 18 Redundancy with IM 152 ET 200iSP 82 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 184: ...Commissioning and Diagnostics 6 8 Diagnostics with STEP 7 ET 200iSP 184 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 194: ...Maintenance 7 7 Reading service data ET 200iSP 194 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 220: ...Terminal modules 9 6 Terminal module TM RM RM ET 200iSP 220 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 372: ...Glossary ET 200iSP 372 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 384: ...Index ET 200iSP 384 Operating Instructions 11 2017 A5E00247483 07 ...