Changing the PROFIBUS DP Address
1. Use the screwdriver to set the PROFIBUS DP address "0" by means of the DIP switch.
2. Switch the supply voltage of the ET 200iSP on and off at the Power Supply PS. The deletion
operation is finished when the BF LED flashes (0.5 Hz, duration approx. 10 s).
The ET 200iSP saves the parameters retentively in the Flash memory of the IM 152.
Therefore you should delete the retentive stored parameters during the initial
commissioning or after the modification of the system.
3. Now set the new PROFIBUS DP address by means of the DIP switch and again switch the
supply voltage on and off at the Power Supply PS.
21
2))
([DPSOH
'3DGGUHVV
UHVHUYHG
,QWHUIDFHPRGXOH
Figure 5-16
Setting the PROFIBUS DP address
Note
If you change the PROFIBUS DP address without previously erasing the retentive parameters
in the Flash memory, the ET 200iSP does not respond with either the new or to the old address
on the PROFIBUS DP.
Wiring
5.6 Setting the PROFIBUS address
ET 200iSP
132
Operating Instructions, 11/2017, A5E00247483-07
Содержание SIMATIC ET 200iSP
Страница 82: ...Configuration options 3 18 Redundancy with IM 152 ET 200iSP 82 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 184: ...Commissioning and Diagnostics 6 8 Diagnostics with STEP 7 ET 200iSP 184 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 194: ...Maintenance 7 7 Reading service data ET 200iSP 194 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 220: ...Terminal modules 9 6 Terminal module TM RM RM ET 200iSP 220 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 372: ...Glossary ET 200iSP 372 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 384: ...Index ET 200iSP 384 Operating Instructions 11 2017 A5E00247483 07 ...