Dimensions for the securing holes
The following table contains the dimensions for the holes for securing mounting rails.
Table 4-3
Diagram for securing mounting rails
"Standard" Mounting Rail
D
E
E
PP
PP
①
Mark for additional bore hole for applications with increased vibration and shock stress.
Length of the
mounting rail
Distance a
Distance b
Maximum number of terminal mod‐
ules
1
within distance b
482.6 mm
8.3 mm
466 mm
6
530 mm
15 mm
500 mm
7
585 mm
8.5 mm
568 mm
8
830 mm
15 mm
800 mm
12
885 mm
8.5 mm
868 mm
13
1
Width of terminal modules: 60 mm
Required tools
Wrench or screwdriver suitable for selected securing screws.
Required accessories
To secure the mounting rail, you can use the following types of screws:
Table 4-4
Securing screws
For
You can use...
Explanation
Outer securing screws
M6 cylinder head screw in accord‐
ance with ISO 1207 / ISO 1580
(DIN 84 / DIN 85)
Select the screw length to suit the
situation.
You also require 6.4 washers to
ISO 7092 (DIN 433)
Hexagon head screw M6 to ISO
4017 (DIN 4017)
Installing
4.2 Installing the mounting rail
ET 200iSP
92
Operating Instructions, 11/2017, A5E00247483-07
Содержание SIMATIC ET 200iSP
Страница 82: ...Configuration options 3 18 Redundancy with IM 152 ET 200iSP 82 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 184: ...Commissioning and Diagnostics 6 8 Diagnostics with STEP 7 ET 200iSP 184 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 194: ...Maintenance 7 7 Reading service data ET 200iSP 194 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 220: ...Terminal modules 9 6 Terminal module TM RM RM ET 200iSP 220 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 372: ...Glossary ET 200iSP 372 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 384: ...Index ET 200iSP 384 Operating Instructions 11 2017 A5E00247483 07 ...