6. Swivel the Ex d isolating plug back into the horizontal position and push it back to the end
stop. Pay attention that the locking lever is flush with the plug and is engaged.
7. Label the electronic module using the labeling strips provided and reinsert the labeling strips
into the electronic module.
Note
If a gap (of an electronic module 2 DO Relay UC60V/2A) develops due to the ET 200iSP
configuration, the following rules apply:
● The gap is at the last slot of the ET 200iSP: insert the slot cover (or a reserve module
as of product version 3 or later) in this gap.
● The gap is at a different slot (for electronic module 2 DO Relay UC60/2A): insert a
reserve module (as of product version 3) in this gap.
Uninstalling electronic modules 2 DO Relay UC60V/2A
1. Follow steps 1 to 3, see "Digital electronic module 2 RO Relay UC60V/2A (Page 254)"
installing and labeling
2. Use the screwdriver to operate the catch on the underside of the electronic module.
3. Swivel this upward.
4. Remove the module from the storage space of the terminal module.
Wiring
5.5 Inserting and labeling the power supply, interface module, and electronic modules
ET 200iSP
130
Operating Instructions, 11/2017, A5E00247483-07
Содержание SIMATIC ET 200iSP
Страница 82: ...Configuration options 3 18 Redundancy with IM 152 ET 200iSP 82 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 184: ...Commissioning and Diagnostics 6 8 Diagnostics with STEP 7 ET 200iSP 184 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 194: ...Maintenance 7 7 Reading service data ET 200iSP 194 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 220: ...Terminal modules 9 6 Terminal module TM RM RM ET 200iSP 220 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 372: ...Glossary ET 200iSP 372 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 384: ...Index ET 200iSP 384 Operating Instructions 11 2017 A5E00247483 07 ...