Distributed over all the automation systems connected to the BCS, the BCS can:
● Have a brief peak load (max. 1 s) of up to 200 simultaneous step changes. In this case, a
maximum of 200 recipe phases that do not execute a step change can also be active. To
ensure that the BCS and AS continue to operate synchronized with each other following
such peak loads, you must ensure a recovery time of that least 60 s.
● Be run in continuous operation with not significantly more than 350 simultaneous, active
recipe phases. In this case, an average of 2 step changes may be active per second.
Result of the determination of memory requirements (data blocks) for AS-based mode
The following table shows the minimum memory requirements (data blocks) of the CPU for
AS-based mode.
Memory allocations
Description
Memory requirements in KB
Static part. Occupied by system.
Communication (Event Send)
56
Function blocks
60
Function calls
41
Dynamic part. Occupied by settings in
the BATCH configuration dialog.
per unit
57
per recipe unit procedure (RUP)
128
Based on the recipe data from the section "Basics for calculating the performance of both
modes", the actual memory requirements can be calculated as shown below.
Note
For this performance determination, the units must be configured within one automation
system and the recipe unit procedures must all be active at the same time.
Sample calculation (AS-based mode only)
Memory allocations
Description
Memory requirements in KB
Static part. Occupied by system.
Communication (Event Send)
56
Function blocks
60
Function calls
41
Dynamic part. Occupied by settings in
the BATCH configuration dialog.
10 units
570
10 simultaneously running recipe unit
procedures (RUP)
1280
Memory requirements
Total in KB:
2007
Based on this calculation, it can be seen that the AS requires at least 2007 KB of memory for
the recipe logic. You set the memory required for the recipe logic as a percentage of the entire
work memory in the BATCH configuration dialog for the CPU.
To determine the amount of required memory for a CPU, you need to add the standard BATCH
blocks (SFC type, SFC, IEPH etc.) and the blocks for process control (drivers, actuators,
sensors etc.).
Product introduction and installation
3.6 Configuration limits
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA
73
Содержание SIMATIC BATCH
Страница 30: ...Security information SIMATIC BATCH V8 2 30 Operating Manual 02 2016 A5E35958174 AA ...
Страница 135: ...Example Engineering 7 1 Basic engineering for PCS 7 SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 135 ...
Страница 403: ...BATCH Control Center 9 8 Batch control SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 403 ...
Страница 584: ...BATCH Recipe Editor 10 5 Other functions SIMATIC BATCH V8 2 584 Operating Manual 02 2016 A5E35958174 AA ...
Страница 722: ...Appendix 13 4 Command line parameters for BatchCC SIMATIC BATCH V8 2 722 Operating Manual 02 2016 A5E35958174 AA ...
Страница 1158: ...Index SIMATIC BATCH V8 2 1158 Operating Manual 02 2016 A5E35958174 AA ...