Result
In the component view, below the configured SIMATIC PC station, you will see the following
object.
7.1.2.5
Adapting the CPU for AS-based mode
Adapt local data
The memory requirements of the local data of your CPU must be calculated for AS-based
mode and then possibly adapted. This is necessary for every CPU in your PCS 7 project.
Procedure
1. Open any CFC chart in the relevant S7 program.
2. Select the menu item Options > Chart Reference Data.
3. Select the menu item View > Local Data.
4. Use the local data table that is displayed in the steps described below.
5. Open your project with the component view in SIMATIC Manager.
6. In the SIMATIC manager, open the HWConfig. hardware configuration
7. Select the CPU in the rack.
8. Use the shortcut menu to select the object properties of the CPU.
9. Click on the "Memory" tab in the open dialog. You will see the local data arranged in priority
classes.
10.Adapt the amount of memory for the local data in accordance with the displayed local data
referred to in point 4.
Note
Optimization of local data
Use the procedure described above to optimize your local data within the priority classes
Engineering
7.1 Basic engineering for PCS 7
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA
129
Содержание SIMATIC BATCH
Страница 30: ...Security information SIMATIC BATCH V8 2 30 Operating Manual 02 2016 A5E35958174 AA ...
Страница 135: ...Example Engineering 7 1 Basic engineering for PCS 7 SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 135 ...
Страница 403: ...BATCH Control Center 9 8 Batch control SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 403 ...
Страница 584: ...BATCH Recipe Editor 10 5 Other functions SIMATIC BATCH V8 2 584 Operating Manual 02 2016 A5E35958174 AA ...
Страница 722: ...Appendix 13 4 Command line parameters for BatchCC SIMATIC BATCH V8 2 722 Operating Manual 02 2016 A5E35958174 AA ...
Страница 1158: ...Index SIMATIC BATCH V8 2 1158 Operating Manual 02 2016 A5E35958174 AA ...