● If you power down both BATCH servers on a redundant system with a time lag, when
restarting the BATCH server you will have to firstly restart the server you powered down
last. If you don't do this, there is a risk of you losing batch measurements and messages
from the period of the time lag.
● When starting and ending database synchronization between the master and standby
servers, the WinCC messages "Data synchronization started" and "Data synchronization
complete" are produced.
5HGXQGDQW
%$7&+VHUYHU
)DXOWWROHUDQW
UHSOLFDWLRQ
VROXWLRQ
'DWDEDVH
V\QFKURQLVDWLRQ
%$7&+
VHUYHU
%$7&+
VHUYHU
7HUPLQDOEXV
3ODQWEXV
Hardware requirements
● Redundant BATCH servers always require an additional network adapter independent from
the terminal and plant bus. These network adapters can be of the same type.
● The additional network adapters must be installed in your PCs (redundant BATCH server
pair) in free PCI slots.
● Make sure that you read the information in the relevant SIMATIC PCS 7 documents,
especially the document
PCS 7 - PC Configuration and Authorization.
Product introduction and installation
3.5 Possible configurations
SIMATIC BATCH V8.2
58
Operating Manual, 02/2016, A5E35958174-AA
Содержание SIMATIC BATCH
Страница 30: ...Security information SIMATIC BATCH V8 2 30 Operating Manual 02 2016 A5E35958174 AA ...
Страница 135: ...Example Engineering 7 1 Basic engineering for PCS 7 SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 135 ...
Страница 403: ...BATCH Control Center 9 8 Batch control SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 403 ...
Страница 584: ...BATCH Recipe Editor 10 5 Other functions SIMATIC BATCH V8 2 584 Operating Manual 02 2016 A5E35958174 AA ...
Страница 722: ...Appendix 13 4 Command line parameters for BatchCC SIMATIC BATCH V8 2 722 Operating Manual 02 2016 A5E35958174 AA ...
Страница 1158: ...Index SIMATIC BATCH V8 2 1158 Operating Manual 02 2016 A5E35958174 AA ...