5. Close the properties dialog, save the recipe, and release it.
Image 12-22 Master recipe for unit selection using condition
6. Create a batch with the master recipe you have just created.
7. Set the input "UnitStatus" at the "UNIT_PLC" block of reactor R502 to the created
enumeration "TA_states" and select the value "dirty". As a result, if there is an allocation
condition for the Reactor unit class, the condition will only be true for Reactor 501, allowing
it to be selected dynamically for further batch execution.
Recommended procedure
12.8 How do I configure and use dynamic unit parameters?
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA
711