If the nominal value is outside of the values of the limits calculated in tooltip then a warning is
issued on release of the recipe even although it is within the nominal value limits.
Example 2
Recipe header
Reference quantity
REF
Recipe
1000 liter
Minimum quantity
LL
Recipe
100 liter
Maximum quantity
HL
Recipe
5000 liter
Unit
Unit_A
Lower limit of nominal value
LL
SP
100 liter
Upper limit of nominal value
HL
SP
1500 liter
Setpoint
SP
250 liter
Amount of mix = 1000kg
As the amount of the mix is identical to the standard mix then no adjustment is made. A single
dosage has a total volume of 250 Kg in the container. The batch is plausible and is released.
Amount of mix = 5,000kg
As the mixed volume is 5 times greater than the standard mix, the nominal value is adjusted
in case of linear adjustment from 250kg to 1250kg. here, the upper limit of 1500 Kg for single
dosages is not exceeded - the batch is released.
Amount of mix = 6,000kg
As the mixed volume is 6 times greater than the standard mix, the nominal value is adjusted
in case of linear adjustment from 250kg to 1,500kg. Here, there are 4 single dosages of 1500kg
resulting in a total volume of 6000kg in the container. There is an overdosage of 1000kg in the
container although the single dosage volumes are within the limits of the single steps. However,
as the system only checks the limits of the single dosages, but does not permit the standard
mix to be exceeded or fallen below, the batch is plausible and is released.
Remedy
The incorrect behavior of this batch can be prevented by making a change to the configuration
at the upper limit of the single step from 1500 Kg to 1250 kg. Engineering and the creator(s)
of the recipe must work together on this. Please carry out the test runs.
BATCH Control Center
9.6 Batch Planning
SIMATIC BATCH V8.2
370
Operating Manual, 02/2016, A5E35958174-AA
Содержание SIMATIC BATCH
Страница 30: ...Security information SIMATIC BATCH V8 2 30 Operating Manual 02 2016 A5E35958174 AA ...
Страница 135: ...Example Engineering 7 1 Basic engineering for PCS 7 SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 135 ...
Страница 403: ...BATCH Control Center 9 8 Batch control SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 403 ...
Страница 584: ...BATCH Recipe Editor 10 5 Other functions SIMATIC BATCH V8 2 584 Operating Manual 02 2016 A5E35958174 AA ...
Страница 722: ...Appendix 13 4 Command line parameters for BatchCC SIMATIC BATCH V8 2 722 Operating Manual 02 2016 A5E35958174 AA ...
Страница 1158: ...Index SIMATIC BATCH V8 2 1158 Operating Manual 02 2016 A5E35958174 AA ...