8.5.6
Errors sources in distributed multiproject engineering with SIMATIC BATCH
Introduction
If the procedures and requirements for individual configurations are not adhered to, the
following errors may occur:
● The batch data in the CMP and all projects may become invalid
● The batch data in the Batch database may become invalid
● SFC types may be changed in the master data library with confirmation.
Troubleshooting
How are problems like this avoided?
Procedure on the ES in the SIMATIC Manager
1. Open the multiproject in the SIMATIC Manager.
2. Remove the ISA-88 type definition and delete the Batch process cell in all AS projects of
the multiproject. The OS projects are an exception to this.
3. Update the Batch process cell, generate and propagate the batch types, merge the batch
instances, and transfer the messages to the OS.
The batch types now only include the types you generated manually. The batch instances
are also empty.
4. Reinsert a Batch process cell and the ISA-88 type definition in all AS projects of the
multiproject. The OS projects are an exception to this; they are retained.
5. Update the Batch process cell, generate and propagate the batch types, merge the batch
instances, transfer the messages to the OS, and download the batch data.
The batch types now also include the generated types again. You have merged the batch
instances.
6. Check if all function blocks and SFC types are identical in all projects of the CMP and have
the same version. The easiest way to ensure this, is to update the function blocks of the
master data library in all projects (AS projects). You can also copy the SFC types to all
chart folders of the S7 program.
– Select the block folder within your S7 program in your integrated project. Select
Options > Charts > Update Block Types. Select the S7 program to be checked and click
Next.
If an update is not required, this is indicated by a check mark in the "Status" check box.
If an update is required, the "Update" dialog is displayed. Select the block types that are
to be updated. Check the log and close the wizard.
– Copy the SFC types in the chart folder of your integrated project to all chart folders within
the CMP.
Rational engineering
8.5 Distributed multiproject engineering
SIMATIC BATCH V8.2
238
Operating Manual, 02/2016, A5E35958174-AA
Содержание SIMATIC BATCH
Страница 30: ...Security information SIMATIC BATCH V8 2 30 Operating Manual 02 2016 A5E35958174 AA ...
Страница 135: ...Example Engineering 7 1 Basic engineering for PCS 7 SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 135 ...
Страница 403: ...BATCH Control Center 9 8 Batch control SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 403 ...
Страница 584: ...BATCH Recipe Editor 10 5 Other functions SIMATIC BATCH V8 2 584 Operating Manual 02 2016 A5E35958174 AA ...
Страница 722: ...Appendix 13 4 Command line parameters for BatchCC SIMATIC BATCH V8 2 722 Operating Manual 02 2016 A5E35958174 AA ...
Страница 1158: ...Index SIMATIC BATCH V8 2 1158 Operating Manual 02 2016 A5E35958174 AA ...