Assigned unit of measure Assign the physical unit of measure to the process tag type parameter from
the drop-down list. You must specify desired units of measure beforehand
under "Units of measure".
"Unit of measure" button Activating this button takes you to the appropriate unit. Use the Back button
on the unit of measure to return to this point.
Archive measured value
A process tag type parameter is selected here if a connection to a WinCC
process tag is to be established. This selection is the prerequisite for as‐
signing a type parameter to process tag archive tag. You make this assign‐
ment subsequently on the instance parameter of the appropriate phase
type.
Test manufacturing in‐
struction
A type parameter is selected here if it is to be provided in the batch log for
the manual check (manufacturing instruction).
Events log ID
Here you can specify a value from 0 - 65535 that can be evaluated later in
a user batch log to allow filtering. Different values are permitted for setpoint
and process value. This means, for example, that you could filter according
to setpoints with setpoint ID ≤ 1000 AND setpoint ID ≥ 500 and according
to process values with process value ID ≤ 2000. The user can specify how
convenient such a query is in his log software.
Created by
Specification of the application that created the object, either SIMATIC
BATCH PCell Control Center or SIMATIC Manager:
● If a type object was created by SIMATIC Manager, additional subobjects
cannot be added, nor can the selected object be deleted or changed,
either via the PCC API or with the PCC configuration dialog.
● If an instance object was created by SIMATIC Manager, additional
subobjects can be added via the PCC API or with the PCC configuration
dialog. However, it is still not possible to delete or change the selected
object here.
Process tag types
Buttons
Update
All batch instances are adapted according to the batch types. This action
is always required if a change has been made to batch types of existing
batch instances (e.g., inserting a new parameter, changing the unit of
measure, etc.).
Delete
The process tag type parameters object can be deleted here. Deletion is
only possible if the selected object is not in use.
Log
"Errors" display field
The number of errors for the selected log is displayed.
"Warnings" display field
The number of warnings for the selected log is displayed.
"Display" button
The logging is activated with the "Display" button. The selected log is
generated as an XML file in the specified layout and displayed in In‐
ternet Explorer.
Select "Process cell" and click the "Display" button to show all process
cell errors or warnings. You can also right-click a selected object and
select the "Display log" function to display object-specific errors or
warnings.
Context help references
14.1 Dialogs
SIMATIC BATCH V8.2
1002
Operating Manual, 02/2016, A5E35958174-AA
Содержание SIMATIC BATCH
Страница 30: ...Security information SIMATIC BATCH V8 2 30 Operating Manual 02 2016 A5E35958174 AA ...
Страница 135: ...Example Engineering 7 1 Basic engineering for PCS 7 SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 135 ...
Страница 403: ...BATCH Control Center 9 8 Batch control SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 403 ...
Страница 584: ...BATCH Recipe Editor 10 5 Other functions SIMATIC BATCH V8 2 584 Operating Manual 02 2016 A5E35958174 AA ...
Страница 722: ...Appendix 13 4 Command line parameters for BatchCC SIMATIC BATCH V8 2 722 Operating Manual 02 2016 A5E35958174 AA ...
Страница 1158: ...Index SIMATIC BATCH V8 2 1158 Operating Manual 02 2016 A5E35958174 AA ...