Procedure
1. Create a new batch with the released master recipe.
2. Open the control recipe of the created batch and ensure that the opened control recipe
window is in the foreground. If the title bar of the dialog is shown in color, then the window
is activated.
3. Start the procedure via the command sequence Control > Structure change > Start. Confirm
the start of OSC processing mode with the "Yes" button.
– In the tree view in BatchCC, the affected batch is highlighted with a blue pen (editing)
and a lock (interlocking).
– In the status bar, the warning dialog "Structure change" is shown to you and all other
associated BATCH clients. You can skip the warning dialog.
– A flashing editing symbol and the text "Batch editing" are also displayed in the status
bar for your information. If you move the cursor to the editing symbol, the warning dialog
is displayed again.
– In a BatchCC window, an advanced toolbar is displayed for editing the batch.
4. Make a change to your control recipe (batch). Insert, for example, an operator instruction
into your control recipe.
– The symbols "Apply structure change" and "Reject all changes" are activated for use in
the toolbar.
– In the menu bar under Control > Structure change, the commands "Accept change" and
"Reject change" are activated for use.
5. If you want to reject your structure change made under point 4:
– In the menu bar, select the command Control > Structure change > Reject change.
– In the menu bar, select the command "Reject all changes".
6. If you want to accept your structure changes made under point 4:
– In the menu bar, select the command Control > Structure change > Accept changes.
– In the toolbar, select the command "Accept all changes".
7. The toolbar is closed after completing the online structure change via point 5 or 6.
– A batch that was paused before the online structure change can be resumed after editing.
– A batch that was released before the online structure change can be started.
– A batch that was planned before the online structure change can be released and started.
Result
You have executed the new commands and procedure for an online structure change.
In the "Change Log" tab of the "Properties" dialog of a batch in the BatchCC, you can display
information that indicates that a structure change has been made to this batch.
BATCH Control Center
9.8 Batch control
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA
465
Содержание SIMATIC BATCH
Страница 30: ...Security information SIMATIC BATCH V8 2 30 Operating Manual 02 2016 A5E35958174 AA ...
Страница 135: ...Example Engineering 7 1 Basic engineering for PCS 7 SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 135 ...
Страница 403: ...BATCH Control Center 9 8 Batch control SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 403 ...
Страница 584: ...BATCH Recipe Editor 10 5 Other functions SIMATIC BATCH V8 2 584 Operating Manual 02 2016 A5E35958174 AA ...
Страница 722: ...Appendix 13 4 Command line parameters for BatchCC SIMATIC BATCH V8 2 722 Operating Manual 02 2016 A5E35958174 AA ...
Страница 1158: ...Index SIMATIC BATCH V8 2 1158 Operating Manual 02 2016 A5E35958174 AA ...