Controllers
6.6 Connecting terminals and interfaces
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
System Manual, 06/2016, A2B00096162-AN
131
6.6.2
Digital input signals
Slot X6
You can connect certain signals for drive functions at the inputs Input 1, Input 2, Input 3,
Input 4 (X6) and Input 0 (X5). The following table shows how the drive function and input are
assigned depending on the controller.
Table 6- 17 Overview of signals for drive functions at slot X6
Slot X6
AT40
ATD400V
ATD400K
ATD400T
RELAY LB
RELAY RC
Accumulator mode
Emergency power mode
Input 1
Light barrier or
DCPS
Light barrier Gate interlock-
ing
Motion detector
Input 2
Nudge
Cord-operated switch
Door locked
Input 3
DOOR CLOSE
Input 4
DOOR OPEN
Input 1, Input 2,
Input 3 and Input 4
inactive
Deenergize (not a door command)
Table 6- 18 Overview of signals for drive functions at slots X5 and X6
Slot X5/X6
ATD401W
Standard input
1)
ATD401W
Emergency stop with 3
inputs
2) 3)
(see Fail-safe digital
control concept)
ATD410W/ATD420W/AT
D430W
Input 0
Emergency
power
mode
NDG
(second
force and
energy
profile)
3)
Stop (inverted)
Parameterizable as local
sensor type or linked with
FBLOCK
Input 1
Parameterizable
(local sensor type)
Parameterizable
(local sensor type)
Input 2
Partial opening operation Partial opening operation Signal logic determined
via PLC and/or linked
with FBLOCK
Input 3
DOOR CLOSE
DOOR CLOSE (inverted)
Input 4
DOOR OPEN
DOOR OPEN (inverted)
Input 1, Input 2,
Input 3 and In-
put 4 inactive
Deenergize (not a door
command)
–
Deenergize (not a door
command)
1)
Adjustable via the service menu
"General setup > Special parameters > FBLOCK configuration >
FBLOCK config. Standard input"
2)
Adjustable via the service menu
"General setup > Special parameters > FBLOCK configuration >
FBLOCK config. Emergency stop 3 inp."
3)
Firmware version 1.03 or higher