![Siemens SIDOOR AT40 Скачать руководство пользователя страница 48](http://html.mh-extra.com/html/siemens/sidoor-at40/sidoor-at40_system-manual_377380048.webp)
Controllers
6.2 Drive functions
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
48
System Manual, 06/2016, A2B00096162-AN
6.2.9
Door locked
Description of function
If the "Door locked" command is active, the door control system responds as follows:
●
The door drive is torque-free.
●
The incoming commands "DOOR OPEN" and "Motion detector" are not evaluated by the
controller.
●
The hold-open time is cancelled.
●
The keyboard lighting is deactivated.
After the "Door locked" command is revoked, the door system becomes active again after a
delay of 3 s. The door then moves in the CLOSE direction.
Connection
The "Door locked" function is connected to "Input 2" (X6). See also Section Digital input
Signals
Signal
Description
1 (voltage applied)
Door interlocking is active
0 (voltage not applied)
Door interlocking is not active