Table 6-6
Pin assignment at terminal block 100 to 240 VAC / 60 to 250 VDC for the power supply
Pin number
Assignment
Pin 1
L (100 to 240 V)
Pin 2
N
Pin 3
FE (functional earth)
To wire up the power connector, use a copper cable of category 18-8 AWG or cable with a
cross-section of 0.75 to 6 mm².
DC voltage is connected at the following terminals:
● Plus to "L"
● M to "N"
Secure the firm seat of connectors and the terminal block by tightening the screws (does not
apply to X‑300EEC).
Connecting
6.7 Power supply
SCALANCE XR-300M EEC
56
Compact Operating Instructions, 11/2019, A5E02661176-14