Functions
Multifunctional input, digital input
4
92 | 150
A6V11545892_en--_a
4.10 Multifunctional input, digital input
The thermostat has 3 multifunctional inputs X1, X2 and U1. Input U1 will be
configured as digital input in a future product version.
An NTC type sensor like NTC 3k, a LG-Ni1000 (AI, analog input) or a switch (DI,
digital input) can be connected to the input terminals. The functionality of the inputs
can be configured via P150 + P151 for X1, P153 + P154 for X2, and P155 + P156
for U1.
The current temperature or state of the inputs X1/X2 and U1 is available on the bus
for monitoring purposes.
The parameters can be set to the following values:
#
Input function
Description
Type
X1/X2/U1
0
Not used
No function
--
1
External/return air
temperature
Sensor input for external room temperature
sensor or return air temperature sensor to acquire
the current room temperature.
AI
Heating/
cooling
changeover
2
Heating/cooling
changeover
Sensor input for "Automatic heating/cooling
changeover" function.
A switch can also be connected rather than a
sensor.
Important: Switching state configured via P151,
P154, P156. See also Additional functions [
Heating/cooling changeover is possible via bus.
In this case, the function must not be assigned to
local inputs X1, X2, U1. See also Additional
42].
Diagnostic value 0
˚
C is displayed for closed
contact, 100
˚
C for open contact, if a switch is
connected.
AI/DI
Window
contact
3
Window contact
Digital input to change over the operating mode
to Protection.
If the window contact is active, user operations
are ineffective and OFF is displayed.
Window contact is also possible via bus. In this
case, do not assign the function to local inputs
X1, X2 or U1. See also Operating modes [
DI
4
Dewpoint monitor
Digital input for dewpoint sensor to detect
condensation. Cooling is stopped in the event of
condensation.
DI
Enable
electric
heater
5
Enable electric heater
Digital input to enable/disable the electric heater
via remote control.
Enable electric heater is also possible via bus. In
this case, do not assign the function to local
inputs X1, X2, U1. See also Control sequences
56].
DI
Fault
information
6
Fault
Digital input to signal an external fault (e.g.: dirty
air filter).
If the input is active, ALx is displayed and a fault
is sent on the bus. See also Fault and alarms
(Alarm x, with x = 1 for X1, x = 2 for X2, x = 3 for
U1).
Note: Fault displays have no impact on
thermostat operation. They merely represent a
visual signal.
DI