Functions
Fan control
4
A6V11545892_en--_a
89 | 150
Combination 1
st
stage
signal
2
nd
stage
signal
Fan type Fan synchro Fan behavior
6
On/off
DC
DC
2
nd
sequence
XpH/XpC,
P/PI control
7
DC
On/off
DC
1
st
sequence XpH/XpC,
P/PI control
8
DC
On/off
DC
2
nd
sequence
XpH
Fan
/XpC
Fan
,
P-control
9
DC
DC
3-speed 1
st
sequence XpH/XpC,
P/PI control
10
DC
DC
3-speed 2
nd
sequence
XpH/XpC,
P/PI control
Fan operation can be limited to be active with cooling only or heating only, or even
disabled via P350.
When fan operation is disabled, the fan symbol on the display disappears and
pressing the fan button has no impact.
This function allows for using the thermostat in universal applications such as
chilled/heated ceilings and radiator, etc. (see Chilled/heated ceiling and radiator
In automatic mode, a dwelling time of 2 minutes (factory setting) is active. The fan
maintains each speed for at least 2 minutes before changing to the next speed.
The minimum on-time can be adjusted from 1…6 minutes via P362.
In automatic fan mode and with the room temperature in the dead zone, the control
valve is normally closed and the fan is disabled. With the periodic fan kick function,
the fan can be released from time to time at low speed for a minimum on-time (see
above) even if the valve is closed.
This function is used to prevent damage from moisture due to a lack of air
circulation, or to allow a return air temperature sensor to acquire the correct room
temperature.
➀
Periodic fan kick
➁
Minimum on-time
Periodic fan kick time can be selected individually for Comfort via P363, and via
P364 for Economy.
●
Fan kick value 0 means the fan runs continuously in the dead zone (only
selectable in Economy via P364)
●
Fan kick value 1 and higher: Value in minutes
●
Fan kick value Off means the fan does not run in the dead zone
The fan speed in the dead zone (Comfort mode) can be set via P029 (Service
level) ask per customer preferences.
To save energy, the manual fan in the dead zone is controller same as the auto fan
(P029 = 3, 4 or 5).
The following options are available:
●
Auto fan does not run in the dead zone (P029 = 0)
●
Auto fan runs in the dead zone at low speed during heating and cooling (P029
= 1)
Fan operation as per
heating/cooling mode, or
disabled
Fan minimum on- time
Periodic Fan kick (P363,
P364)
Notes
Fan stage in dead zone
P029