Functions
Control parameters
4
A6V11545892_en--_a
113 | 150
4.15.5 Expert level parameters with diagnostics and test
Para
meter
Name
Fa
cto
ry
s
et
ting
Ran
ge
RDG2
00
KN
RDG2
60
KN
Dep
en
den
cie
s
Expert level
Control settings
P050
Heat P-band Xp
2 K
0.5…6 K
✓
✓
‒
P051
Switching differential heating
1 K
0.5…6 K
✓
✓
‒
P052
Cool P-band Xp
P053
Switching differential cooling
P054
Radiator P-band Xp/switching
differential
2 K
0.5…6 K
✓
✓
‒
P055
Dead zone Comfort mode
2 K
0.5…5 K
✓
✓
‒
P056
Setpoint differential
2 K
0.5…5 K
✓
✓
‒
P057
1)
Integral action time Tn for heating
45 min
0...120 min
✓
✓
P201,
P203,
P204
P058
1)
Integral action time Tn for cooling
P059
2)
H/C changeover switching point
cooling
16 °C (61 °F) 5 °C…P060-2 K (41 °F…P060-2 K)
✓
✓
P001,
P150,
P153,
P155
P060
2)
H/C changeover switching point
heating
28 °C (82 °F) P059+2 K…40 °C (P059+2 K…104 °F)
✓
✓
P001,
P150,
P153,
P155
P063
Minimum supply air temperature
OFF
OFF, 0 °C…P064 (32 °F…P064)
✓
✓
P150,
P153,
P155
P064
Maximum supply air temperature
OFF
OFF, P063…50 °C (P063…122 °F)
✓
✓
P150,
P153,
P155
Mode and setpoints
P100
Protection heating setpoint
8 °C (46 °F)
OFF, 5 °C…P101; (41 °F…P101)
✓
✓
‒
P101
Protection cooling setpoint
OFF
OFF, P100…40 °C; (P100…104 °F)
✓
✓
‒
P102
3)
Temporary Comfort mode
OFF
OFF, 1...360 min
✓
✓
P002
P103
Temporary Comfort setpoint
OFF
0 = Disabled (OFF)
1 = Enabled (ON)
2 = Enabled (ON), excluded Window
contact
3 = Enabled (ON), excluded presence
detector (include hotel presence)
✓
✓
‒
P104
Setpoint display
1
1 = Absolute setpoints
2 = Relative setpoints
✓
✓
‒
P110
Energy indicator
1
OFF = Disabled
1 = Green and Red dimmed out
2 = Green dimmed out / Red fixed
3 = Green and Red fixed
✓
✓
‒
P111
Energy indicator range
2 K
0…10 K
✓
✓
‒