Functions
Control parameters
4
112 | 150
A6V11545892_en--_a
Para
meter
Name
Fa
cto
ry
s
et
ting
Ran
ge
RDG2
00
KN
RDG2
60
KN
Dep
en
den
cie
s
Service level
P026
Humidity setpoint low
OFF
OFF (0), 20…90 % or P024
✓
✓
P450
P027
3)
Electric heater when cooling
ON
ON: Enabled
OFF: Disabled
✓
✓
Appl
P028
Keypad
0
0 = Unlocked
1 = Auto lock
2 = Manual lock
3 = Lock the operating mode
4 = Lock the Setpoint shift
5 = Lock fan speed
6 = Lock operating mode and setpoint
shift
7 = Lock operating mode and fan
speed
8 = Lock setpoint shift and fan speed
✓
✓
‒
P029
Fan: Dead zone Comfort mode
2)
0
0 = Fan disable
1 = Low speed (Heat and Cool)
2 = Low speed (Cooling only)
3 = Fan disable Auto & Manual
4 = Low speed (Heat and Cool) Auto
& Manual
5 = Low speed (Cooling only) Auto &
Manual
✓
✓
P350
P030
Buzzer function
ON
ON = Enabled
OFF = Disabled
✓
✓
‒
P031
Language
1
1 = English
2 = French
3 = German
4 = Italian
5 = Spanish
6 = Dutch
7 = Turkish
8 = Czech
9 = Finnish
10 = Polish
11 = Hungarian
12 = Slovak
13 = Romanian
14 = Danish
15 = Norwegian
✓
✓
‒
Note: Parameter display depends on selected application and function. Appl
means application.
1)
P001 cannot be set to 3 if P002 is set to 3, and vice versa.
2)
If P350 = 0, P003 is disabled. P029 is invisible.
3)
Only available when application is 2-pipe with electric heater