Functions
Control sequences
4
70 | 150
A6V11545892_en--_a
The diagrams below show the control sequence for modulating PI control.
Heating mode with manual selection
(P001 = 3)
Cooling mode with manual selection
(P001 = 3)
Heating and cooling (P001 = 4)
T[°C] Room temperature
w Room temperature
setpoint
YE Control command “EI
heater”
YH Control command
"Valve" (heating)
YC Control command " Valve "
(cooling)
XpH Proportional band
"Heating" (P050)
XpC Proportional band "Cooling"
(P052)
X
dz
Dead zone (P055)
w
D
Setpoint differential
(P056)
The diagrams only show the PI thermostat’s proportional part.
For setting sequence and control outputs, see Application overview [
Sequence overview (setting via P001) [
●
YH can only be DC, On/Off or PWM
●
YC can be DC, On/Off, On/Off 3-wired, PWM or 3-position
●
YE can only be DC, On/Off or PWM
Modulating control:
3-position or PWM