Overview
Functions
2
A6V11545892_en--_a
9 | 150
●
Room temperature control via built-in temperature sensor or external room
temperature/return air temperature sensor
●
Room relative humidity control via built-in humidity sensor (humidity function
can be disabled.)
●
Min./max. humidity control by shifting temperature setpoint and releasing
contact for dehumidifier/humidifier
●
Floor heating temperature limitation
●
Min. and max. supply air temperature limitation
●
Selection of operating modes via operating mode button
●
Button lock for all buttons independently (automatically or manually)
●
Changeover between heating and cooling mode (automatic via local sensor or
bus, or manually)
●
Parameters protected by password (disabled by default)
●
Purge function together with 2-port valve
●
Valve exercising function to prevent gripping
●
Reminder to clean fan filters
●
Min. and max. limitation of room temperature setpoint:
– Comfort limitation (min. and max. limitation)
– Energy saving concept (min. and max. limitation separate for heating and
cooling)
●
Temporary Comfort mode extension
●
Green leaf indication function
●
Display of current room temperature or setpoint in
℃
,
℉
or both
●
Application selection via DIP switches or external commissioning software
(ACS, ETS and Siemens smartphone application PCT Go for Android)
●
Parameter download with external commissioning software (ACS, ETS and
Siemens smartphone application PCT Go for Android)
●
Reloading factory settings for commissioning and control parameters
●
1-speed, 3-speed or DC 0...10 V fan control on RDG200KN and RDG260KN
(automatic or manual fan)
●
Advanced fan control function, e.g. fan kick, fan start delay, selectable fan
operation (enable, disable, depending on heating/cooling mode, or min. and
max. speed setting)
●
Fan start depending on fan coil temperature (heating) to avoid cool air while
heating
●
Enabling fan output only in the 2
nd
stage (2-pipe/2-stage)
●
Switching fan speed from manual to automatic in the dead zone to avoid
energy waste (selectable function)
●
Swap function for 2-pipe and 2-stage application by switching the 1
st
stage
heating to 2
nd
stage cooling
●
On 2-pipe/2-stage application, limit the number of heating or cooling sequence
to one
●
Control of 6-port ball valve for chilled and heated ceiling, DC 0…10 V,
DC 2…10 V and inverted signals DC 10…0 V, DC 10…2 V (RDG260KN)
●
Control of 6-port ball valve as changeover (On/Off – open/close signal) and
PICV DC 0…10 V for
– Chilled and heated ceiling/floor (RDG260KN)
– Fan coil application (RDG260KN)
General functions
Setpoints and display
Setting
Fan
Special functions