6.3.2 Relay functions
2-pipe fan coil application, fan coil unit off during Protection mode.
Commissioning
Outputs used
●
Fan P351 = 3
(or DIP6 = OFF)
●
Valve P201 = 5
●
Relay function P402 = 1
(Protection mode)
●
M1 DC 0...10 V fan
●
V1 DC valve
●
L3
*)
Fan coil
●
K Relay
*)
Release contact
140] for min. and
max. ratings
RDG260KN
4-pipe fan coil application, pumps on during heating and cooling demand.
Commissioning
Outputs used
●
Fan P351 = 3
(or DIP6 = OFF)
●
Valve P201/P203 = 5
●
Relay function P401 = 3
(heating pump)
●
Relay function P402 = 4
(cooling pump)
●
M1 DC 0...10 V
fan
●
V1, V2 DC valve
●
L2
*)
Heating pump
●
L3
*)
Cooling pump
●
K Relay
*)
Release contact
140] for min. and
max. ratings
RDG260KN
Example 1:
Switching off the fan coil
unit
Example 2:
Switching on pumps