5
Hardware installation
NE8001 housing solution for NK823x
28
Building Technologies
A6V10854379_a_en
CPS Fire Safety
25.01.2019
NKA8011-A1 mounting plate
7.2
NE8001 housing solution for NK823x
The NE8001 cabinet offers a compact and convenient housing solution for the
NK823x Ethernet Ports. The metallic cabinet allows for an easy wall-mounting. It
includes a DIN rail and a prewired power supply for the NK823x unit and local I/O.
7.2.1
NE8001 hardware requirements
Environmental requirements
The cabinets should always be installed in a clean and safe environment, away
from dust, high temperature and humidity, vibrations and impacts. Conditions and
power supply should match the specific requirements given in the Technical data
section of the NK8237 datasheet.
NE8001 power requirements.
Item
Power supply requirement
Input voltage
100-240 Vac, 50-60Hz
Input current
2A
Note: A switch-box including a bipolar cut-out (phase + neutral) is required in the
electrical installation.
7.2.2
NE8001 hardware installation
The cabinet is typically wall-mounted. A proper support must be provided for the
maximum weight (see Technical data on the NK8237 datasheet). Four supporting
screws or hooks (min. 10 mm) are required.