Full error description
A0 06:
The command code for the started command is not valid (not defined). The correct CC must
be entered (see section 3.4).
A0 11:
– for the first command block: DBN (= byte 8/9 in the telegram) does not have the value
0001.
– for subsequent block: DBN from the user is not in the correct ascending sequence or the
CC parameter (= byte 4) is not appropriate for the command now being processed.
A0 16:
The file handler is currently processing a command from another user. Command processing
will be delayed until the other user is finished. The command may have to be issued again.
B0 01:
Fault in connection to the SLG.
– cable between ASM and SLG is incorrectly wired or cable is damaged
– 24 V supply is not connected or is switched off
– fuse on the ASM is defective
– Hardware fault: ASM 421 or SLG
This error does not occur at the start of the system commands (RESET, NEXT,
ASM STATUS).
B0 02:
EAKO 1, 2:
– A command has been started, but there is no MDS in the transmission
window of the SLG.
– MDS 507; dialog battery is dead (Batt2 bit is not set; measure battery
voltage).
EAKO 0, 2, 3: – the old/current MDS is out of the transmission window and the next/new
MDS has entered the transmission window. A command has been started
(not NEXT). This command refers to the new MDS, but the old/current
MDS has not been terminated with NEXT.
– a new MDS entered the transmission window of the SLG and left it again
without any command being processed. (MDS has “slipped through”).
EAKO 2:
The arrival of an MDS was recognized by the proximity switch on DI 0; how-
ever no MDS is to be found in the transmission window of the SLG.
B0 05:
Only when EAKO (I/O Control) = 3:
No MDS is to be found between points E and A; in this state the departure proximity
switch has been activated.
– an MDS has exited the transmission window without having entered it previously.
– after the departure of an MDS, the MDS has been moved back and the departure proxi-
mity switch activated a second time.
B0 06:
Only when EAKO = 3: MDS generates an entry signal at DI0 but the old MDS has not exited
completely.
– entry (DI0) and exit (DI1) proximity switches are being triggered simultaneously
– entry and exit are too close together
B0 07:
Only when EAKO = 3: two MDS entries have occurred at DI0, but no MDS exited at DI1
– entry and exit are too close together
– an MDS is stationary directly after entry and is moved backwards slightly by the
conveyor