Siemens MICROMASTER Vector MMV110 Скачать руководство пользователя страница 30

E

En

ng

glliis

sh

h

3

3.  

.  IIN

NS

ST

TA

AL

LL

LA

AT

TIIO

ON  

N  

–  

–  

M

MIID

DIIM

MA

AS

ST

TE

ER  

R  

V

Ve

ec

ctto

or  

r  

G85139-H1751-U529-D1

G85139-H1751-U529-D1

© Siemens plc 1999

© Siemens plc 1999

4/8/99

4/8/99

30

30

3.2.2 

3.2.2  Control 

Control Connections

Connections

Control connections to the MIDIMASTER Vector are made via two terminal blocks located as shown in Figure

Control connections to the MIDIMASTER Vector are made via two terminal blocks located as shown in Figure
3.2.1. The terminal blocks are of a two-part design. The part containing the screw terminals can be unplugged

3.2.1. The terminal blocks are of a two-part design. The part containing the screw terminals can be unplugged
from  it’s  housing  before  wires  are  connected.  When  all  connections  to  the  terminals  have  been  made  (

from  it’s  housing  before  wires  are  connected.  When  all  connections  to  the  terminals  have  been  made  (

as

as

shown in Figures 3.2.1 and 3.2.2 

shown in Figures 3.2.1 and 3.2.2 

) and secured, the terminal block must be plugged firmly back into it’s housing.

) and secured, the terminal block must be plugged firmly back into it’s housing.

1

1

2

2

3

3

4

4

8

 

8

 

5

5

6

6

7

7

9

1

9

10

0

1

11

1

Power Supply 

Power Supply 

for PID Feedback 

for PID Feedback 

Transducer 

Transducer 

(+15 V, max. 50 mA)

(+15 V, max. 50 mA)

Power Supply 

Power Supply 

(+10 V, max. 10 mA)

(+10 V, max. 10 mA)

 An

 Ana

alo

logu

gue 

e In

Inpu

put 

t 1

1

-10 V to +10 V 

-10 V to +10 V 

0/2

0/2

 1

 10 

0 V 

 (input impedance 70 k 

 (input impedance 70 k 

 )

 )

o

or 

0/4

0/4

 20 mA )

 20 mA )

(Resistance = 300 

(Resistance = 300 

 )

 )

Output Relays (RL1 and RL2)

Output Relays (RL1 and RL2)
max. 0.8 A / 230 V AC 

max. 0.8 A / 230 V AC 

(overvoltage cat.2)

(overvoltage cat.2)

2.0 A / 30 V DC 

2.0 A / 30 V DC 
(resistive rating)

(resistive rating)

Digital Inputs

Digital Inputs

(7.5 - 33 V, max. 5 mA)

(7.5 - 33 V, max. 5 mA)

P

P1

10

0+

+

0

0V

V

A

AIIN

N+

+

A

AIIN

N--

P15+

P15+

D

DIIN

N1

1 D

DIIN

N2

2

D

DIIN

N3

3

PIDIN-

PIDIN-

Control Terminals

Control Terminals

D

DIIN

N4

4

P

PIID

DIIN

N+

+

 A

 Ana

nalo

logu

gue 

e in

inpu

put 

t 2 

10 

10 V 

o

or 

20 mA

20 mA

 An

 Anal

alog

ogu

ue 

e O

Ou

utp

tpu

ut 

t 2 

0/4 - 20 mA

0/4 - 20 mA

(500 

(500 

 load)

 load)

use with terminal 13

use with terminal 13

 A

 Ana

nallog

ogue 

ue O

Out

utp

put 

ut 1

1

0/4 - 20 mA

0/4 - 20 mA

(500 

(500 

 load)

 load)

1

12

1

2

13

1

3

14

4

1

15

5

1

19

9

1

16

6

1

17

7

1

18

8

2

20  

0  

 A

 A1

1O

OU

UT

T+

+ A

 AO

OU

UT

T-- P

PT

TC

C

P

PT

TC  

C   D

DIIN

N5

5 D

DIIN

N6 

Digital Inputs

Digital Inputs

(7.5 - 33 V, max. 5 mA)

(7.5 - 33 V, max. 5 mA)

Motor temp.protection input 

Motor temp.protection input 

RL1A

RL1A

(NC)

(NC)

RL1B

RL1B

(NO)

(NO)

RL1C 

RL1C 

(COM)

(COM)

2

21

1

2

22 

RL2B

RL2B

(NO)

(NO)

RL2C 

RL2C 

(COM)

(COM)

N

N--

 A

 A2

2O

OU

UT

T+

+

P

PE 

P5V+

P5V+

P

P+

+

2

23

3

2

24

4

2

25

5

2

26  

6   2

27 

RS485 

RS485 

(for USS protocol)

(for USS protocol)

Note:

Note:

 For 

 For PTC motor th

PTC motor thermal 

ermal 

protection, 

protection, P087 

P087 = 

= 1

1

Front Panel 

Front Panel 

RS485 D-type

RS485 D-type

N

N--

0

0V 

5V(max.250mA)

5V(max.250mA)

P

P+

+

PE (case)

PE (case)

1

1

9

9

Figure 

Figure 3.2.2: 

3.2.2:  Control 

Control Connections 

Connections - 

-  MIDIMASTER 

MIDIMASTER Vector 

Vector 

Note:

Note:

Do  not  use  the  internal  RS485  connections  (terminals  24  and  25)  if  you  intend  using  the  external

Do  not  use  the  internal  RS485  connections  (terminals  24  and  25)  if  you  intend  using  the  external
RS485 connection on the front panel e.g. to connect an Clear Text Display (OPM2).

RS485 connection on the front panel e.g. to connect an Clear Text Display (OPM2).

DIP  switches 

DIP  switches  select  between 

select  between voltage  (V) 

voltage  (V) and  current 

and  current ((

II

)  analogue  inputs.  They  also  select  between  either  a

)  analogue  inputs.  They  also  select  between  either  a

voltage or current PID feedback signal (

voltage or current PID feedback signal (

see Figure 4.1.2: DIP Selector Switches

see Figure 4.1.2: DIP Selector Switches

). These switches can only be

). These switches can only be

accessed when:

accessed when:

••

for 

for Frame si

Frame size 

ze 4, 

4, 5 

5 and 

and 6 

6 the 

the front 

front cover 

cover is 

is  removed

removed

(see Figure 3.2.1).

(see Figure 3.2.1).

••

for Frame 

for Frame size 7 

size 7 the lower 

the lower front cover 

front cover is removed 

is removed ((

see Figure 3.2.1

see Figure 3.2.1

).

).

3.2.3 Motor Overload Protection

3.2.3 Motor Overload Protection

When operated below rated speed, the cooling effect of fans fitted to the motor shaft is reduced. so that most

When operated below rated speed, the cooling effect of fans fitted to the motor shaft is reduced. so that most
motors require de-rating for continuous operation at low frequencies. For protection measures using a PTC see

motors require de-rating for continuous operation at low frequencies. For protection measures using a PTC see
section 2.2.5.

section 2.2.5.

Содержание MICROMASTER Vector MMV110

Страница 1: ...ION MIDIMASTER MIDIMASTER Vector Vector 25 25 4 4 CONTROLS CONTROLS AND AND BASIC BASIC OPERATION OPERATION 32 32 5 5 OPERATING OPERATING MODES 36 MODES 36 6 6 SYSTEM SYSTEM PARAMETERS PARAMETERS 41 41 7 7 FAULT FAULT AND AND WARNING WARNING CODES 65 CODES 65 8 8 SPECIFICATIONS SPECIFICATIONS 67 67 9 9 SUPPLEMENTARY SUPPLEMENTARY INFORMATION 73 INFORMATION 73 MICROMASTER MICROMASTER Vector Vector ...

Страница 2: ...23 3 2 2 2 2 6 6 B Bl lo oc ck k D Di ia ag gr ra am m M MI IC CR RO OM MA AS ST TE ER R V Ve ec ct to or r 2 24 4 3 3 I In ns st ta al ll la at ti io on n M MI ID DI IM MA AS ST TE ER R V Ve ec ct to or r 25 25 3 3 1 1 M Me ec ch ha an ni ic ca al l I In ns st ta al ll la at ti io on n 2 25 5 3 3 2 2 E El le ec ct tr ri ic ca al l I In ns st ta al ll la at ti io on n 2 28 8 3 3 2 2 1 1 P Po ow we...

Страница 3: ...7 7 F Fa au ul lt t a an nd d W Wa ar rn ni in ng g C Co od de es s 65 65 7 7 1 1 F Fa au ul lt t C Co od de es s 6 65 5 7 7 2 2 W Wa ar rn ni in ng g C Co od de es s 6 66 6 8 8 S Sp pe ec ci if fi ic ca at ti io on ns s 67 67 9 9 S Su up pp pl le em me en nt ta ar ry y I In nf fo or rm ma at ti io on n 73 73 9 9 1 1 A Ap pp pl li ic ca at ti io on n E Ex xa am mp pl le e 7 73 3 9 9 2 2 U US SS S ...

Страница 4: ... the inverter to restart automatically after an input inverter to restart automatically after an input power failure power failure This This equipment equipment is c is capable of apable of providing providing internal internal motor overload protection in accordance with motor overload protection in accordance with UL508C UL508C section section 42 42 Refer Refer to to P074 P074 Moto Moto overload...

Страница 5: ...minal current current The The motor motor data data parameters parameters must must be be accurately accurately entered entered P080 P085 and P080 P085 and an an auto auto calibration performed P088 1 calibration performed P088 1 before the motor before the motor is started is started Unstable unpredictable Unstable unpredictable motor operation eg reverse rotation may result if this is not done m...

Страница 6: ...rivativ ral Derivative PID e PID control loop control loop function function 15 V 50 mA supply provided for feedback transducer 15 V 50 mA supply provided for feedback transducer Remote control Remote control capability capability via RS485 via RS485 serial li serial link using nk using the USS the USS protocol w protocol with the ith the ability to ability to control up control up to 31 to 31 inv...

Страница 7: ...Do not install the water hazards e g Do not install the inverter beneath inverter beneath pipes that are subject to pipes that are subject to condensation Avoid installing condensation Avoid installing the inverter where excessive humidity and the inverter where excessive humidity and condensation may occur condensation may occur Ensure that the inverter s air vents are not obstructed Ensure that ...

Страница 8: ...r an r and en d ensur sure th e that a at a good electrical connection is made between the heatsink and the panel removing paint if necessary good electrical connection is made between the heatsink and the panel removing paint if necessary 3 3 Whe Wherev rever po er possi ssible ble use use scr screen eened l ed lead eads for s for con connec nectio tions t ns to the o the con contro trol ci l cir...

Страница 9: ...Frame Size B MAINS POWER INPUT MAINS POWER INPUT METAL BACK PLATE METAL BACK PLATE FOOTPRINT FILTER FOOTPRINT FILTER CONTROL CONTROL CABLE CABLE CONTROL CONTROL CABLE CABLE Fix motor and control cable screens Fix motor and control cable screens securely to metal back plate using securely to metal back plate using suitable clips suitable clips EARTH BRAID EARTH BRAID EARTH BRAID EARTH BRAID MAINS P...

Страница 10: ...ICROMASTER and MIDIMASTER Vector The MICROMASTER and MIDIMASTER Vector inverters will operate without nuisance tripping with inverters will operate without nuisance tripping with an RCD an RCD also called ELCBs or RCCBs fitted to the input providing also called ELCBs or RCCBs fitted to the input providing A A type type B B RCD RCD is is used used The trip The trip limit limit of of the the RCD RCD...

Страница 11: ...h 2 th 2 3 3 years years but but the ste the steps sh ps should be ould be 2 hours 2 hours preparation preparation time 8 time 8 hours hours 1 3 4 1 3 4 Operation Operation with Long with Long Cables Cables Motor cable lengths vary depending on type of cable power rating and voltage rating and in some cases can Motor cable lengths vary depending on type of cable power rating and voltage rating and...

Страница 12: ...ing instructions qualified personnel in compliance with the warnings laid down in these operating instructions Take particular note of general and regional installation safety regulations regarding work on Take particular note of general and regional installation safety regulations regarding work on dangerous voltage installations e g VDE as well as the relevant regulations regarding the correct d...

Страница 13: ... washers and nuts MICROMASTER Vector inverters must be secured to a suitable vertical surface by bolts washers and nuts Frame size A units need two bolts or can be DIN rail mounted Frame size B and C units require four bolts Frame size A units need two bolts or can be DIN rail mounted Frame size B and C units require four bolts Figure 2 1 1 Figure 2 1 1 MICROMASTER Vector MICROMASTER Vector Frame ...

Страница 14: ...Model MMVxxx MMVxxx 1 AC 230V 1 AC 230V Class A Class A Filter Filter MMVxxx 2 MMVxxx 2 1 3 AC 1 3 AC 230V 230V Without Without Filter Filter MMVxxx 3 MMVxxx 3 3 AC 380 3 AC 380 500V 500V Without Without Filter Filter Frame Sizes Frame Sizes all measurements in mm all measurements in mm MMV12 MMV12 MMV25 MMV25 MMV37 MMV37 MMV55 MMV55 MMV75 MMV75 MMV110 MMV110 MMV150 MMV150 MMV220 MMV220 MMV300 MMV...

Страница 15: ... L3 3 L2 L2 L1 L1 P PE E P PE E P PE E V V V V U U U U MOTOR MOTOR FUSES FUSES CONTACTOR CONTACTOR FILTER FILTER L L3 3 MICROMASTERVector MICROMASTERVector L L1 1 L L2 2 L3 L3 L L2 2 L L1 1 P PE E P PE E P PE E V V V V U U U U MOTOR MOTOR THREEPHASE THREEPHASE TYPICAL INSTALLATION TYPICAL INSTALLATION SINGLE PHASE SINGLE PHASE Figure 2 2 1 Figure 2 2 1 MICROMASTER Vector Connectors MICROMASTER Vec...

Страница 16: ...ng beneath the inverter inverter Frame size C Frame size C use a small bladed screwdriver use a small bladed screwdriver as shown in Figure 2 2 3 as shown in Figure 2 2 3 to release the gland plate and the to release the gland plate and the fan housing allow them both to swing down to hang beneath the inverter fan housing allow them both to swing down to hang beneath the inverter Connect the cable...

Страница 17: ... and earth PE as shown in Figure 2 2 1 using a 3 core cable for single phase units or a 4 core cable for and earth PE as shown in Figure 2 2 1 using a 3 core cable for single phase units or a 4 core cable for three phase units For the cross section of each core see section 8 three phase units For the cross section of each core see section 8 4 4 Use a 4 core screened Use a 4 core screened cable to ...

Страница 18: ...nd E to release the gland plate and then remove the metal gland plate gland plate and then remove the metal gland plate from the inverter from the inverter 1 1 Insert the blade of a small sc Insert the blade of a small screwdriver into slot A in the rewdriver into slot A in the front of the inverter and press in the direction of the arrow front of the inverter and press in the direction of the arr...

Страница 19: ...ully measure and cut the cable cut the cable leads for the leads for the control connections control connections if required Feed the if required Feed the control cable control cable through the correct gland see Figure 2 2 2 and secure the gland to the metal gland plate through the correct gland see Figure 2 2 2 and secure the gland to the metal gland plate 10 10 Carefully feed the power and cont...

Страница 20: ...and p d pla late te re rele leas ase t e tab abs s D D C Co on nt tr ro ol l c ca ab bl le e i in np pu ut t E E M Ma ai in ns s c ca ab bl le e i in np pu ut t F F M Mo ot to or r c ca ab bl le e o ou ut tp pu ut t G G B Br ra ak ki in ng r g re es si is st to or r D DC C l li in nk c k ca ab bl le i e in np pu ut t H H J J H H F Fa an n c co on nn ne ec ct to or r J J F Fa an n H Ho ou us si in ...

Страница 21: ...for three phase units For able for three phase units For the cross section of each core see section 8 the cross section of each core see section 8 5 5 Use a 4 core Use a 4 core screened cable to screened cable to connect the motor connect the motor 6 6 Carefully measure and cut the cable Carefully measure and cut the cable leads for power connections motor connections leads for power connections m...

Страница 22: ... RL1A RL1A NC NC RL1B RL1B NO NO RL1C RL1C COM COM RL2B RL2B NO NO RL2C RL2C COM COM P P P PE E P5V P5V N N 2 23 3 2 24 4 2 25 5 2 26 6 RS485 RS485 for USS protocol for USS protocol Note Note ForPTCmotorthermal ForPTCmotorthermal protection P087 1 protection P087 1 Front Panel Front Panel RS485 D type RS485 D type N N 0 0V V 5V max 250mA 5V max 250mA P P PE case PE case 6 6 1 1 5 5 9 9 Figure 2 2 ...

Страница 23: ...ed motors require de rating for continuous operation at low frequencies To ensure that motors are protected against overheating under these conditions it is strongly recommended that a PTC temperature sensor is fitted against overheating under these conditions it is strongly recommended that a PTC temperature sensor is fitted to the motor and connected to the inverter control terminals as shown in...

Страница 24: ...3 L L1 N L2 L3 4 4 B B 15 15 26 26 25 25 24 24 23 23 22 22 21 21 20 20 13 13 14 14 5 5 PE PE B DC B DC 1 1 10V 10V 0 0V V O OR R P PE E 16 16 0 10V 0 10V 2 10V 2 10V 0 20mA 0 20mA 4 20mA 4 20mA I I AIN1 AIN1 AIN1 AIN1 PE PE 4 7 k 4 7 kΩ Ω AOUT AOUT AIN2 PID AIN2 PID R RL L2 2 P P N N RS485 RS485 A AD D AIN2 PID AIN2 PID 6 6 7 7 8 8 9 9 12 12 24 24V V 10 10 11 11 O OR R 15V 15V DIN1 DIN1 DIN2 DIN2 ...

Страница 25: ...E as well as the relevant regulations regarding the correct on high voltage installations e g VDE as well as the relevant regulations regarding the correct use of tools and personal protective gear use of tools and personal protective gear Mount the inverter vertically to a flat non combustible surface Make sure that the unobstructed Mount the inverter vertically to a flat non combustible surface ...

Страница 26: ...th D H1 H1 Depth D Depth D H H H H H1 H1 8 5 mm 8 5 mm Frame Sizes 4 5 and 6 Frame Sizes 4 5 and 6 4 bolts M8 4 bolts M8 4 nuts M8 4 nuts M8 4 washers M8 4 washers M8 W1 W1 W1 W1 W W W W 8 5 mm 8 5 mm 6 bolts M8 6 bolts M8 6 nuts M8 6 nuts M8 6 washers M8 6 washers M8 Frame Size 7 Frame Size 7 Figure 3 1 2 Figure 3 1 2 Mechanical Installa Mechanical Installation Diagram M tion Diagram MIDIMASTER V...

Страница 27: ...0 0 x x 2 21 10 0 2 23 35 5 5 53 30 0 6 6 2 27 75 5 x x 6 65 50 0 x x 2 28 85 5 2 23 35 5 6 63 30 0 7 7 4 42 20 0 x x 8 85 50 0 x x 3 31 10 0 3 37 74 4 8 83 30 0 IP20 NEMA 1 with integrated EMC IP20 NEMA 1 with integrated EMC class A filter class A filter W W H H D D W W1 1 H H1 1 4 4 27 275 5 x 7 x 700 00 x x 21 210 0 23 235 5 68 680 0 5 5 2 27 75 5 x x 8 80 00 0 x x 2 21 10 0 2 23 35 5 7 78 80 0...

Страница 28: ...tors on the MIDIMASTER Vector are shown in Figure 3 2 1 DC DC DC DC D DC C D DC C W W L L1 1 L L2 2 L L3 3 P PE E P PE E 20 20 19 19 18 18 17 17 16 16 15 15 14 14 13 13 12 12 11 11 10 10 9 9 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 L L1 1 L L2 2 W W V V U U L3 L3 V V U U 27 27 26 26 25 25 24 24 23 23 22 22 2 2 3 3 1 1 4 4 6 6 5 5 21 21 FS4 5 units FS4 5 units FS6 units FS6 units FS7 units FS7 units PE PE V...

Страница 29: ...nected correctly and the equipment is properly earthed sections 3 2 1 and 3 2 2 Ensure that the leads are connected correctly and the equipment is properly earthed Frame size 4 and 5 Frame size 4 and 5 Tighten up each of the power and motor terminal screws to 1 1 Nm Tighten up each of the power and motor terminal screws to 1 1 Nm Frame size 6 Frame size 6 Tighten up each of the power and motor ter...

Страница 30: ... 1 3 14 4 1 15 5 1 19 9 1 16 6 1 17 7 1 18 8 2 20 0 A A1 1O OU UT T A AO OU UT T P PT TC C P PT TC C D DI IN N5 5 D DI IN N6 6 Digital Inputs Digital Inputs 7 5 33V max 5mA 7 5 33V max 5mA Motortemp protectioninput Motortemp protectioninput RL1A RL1A NC NC RL1B RL1B NO NO RL1C RL1C COM COM 2 21 1 2 22 2 RL2B RL2B NO NO RL2C RL2C COM COM N N A A2 2O OU UT T P PE E P5V P5V P P 2 23 3 2 24 4 2 25 5 2...

Отзывы: