9 Electro-Magnetic Compatibility
Issue 04/02
MICROMASTER 410 Operating Instructions
72
6SE6400-5EA00-0BP0
Case 3: Filtered - for residential, commercial and light industry
This level of performance will allow the manufacturer / assembler to self-certify
compliance of their apparatus with the EMC directive for the residential,
commercial and light industrial environment as regards the EMC performance
characteristics of the power drive system. Performance limits are as specified in
the generic emission and immunity standards EN 50081-1 and EN 50082-1.
Table 9-3
Case 3 - Filtered for Residential, Commercial and Light Industry
EMC Phenomenon
Standard
Level
Emissions:
Radiated Emissions*
EN 55022
Level for equipment class B
Conducted Emissions
EN 61800-3
category C1: level according EN 55011,
class B
category C2: level according EN55011,
class A
Immunity:
Supply Voltage Distortion
EN 61000-2-4
Voltage Fluctuations, Dips, Unbalance,
Frequency Variations
EN 61000-2-1
Electrostatic Discharge
EN 61000-4-2
8 kV air discharge
Burst Interference
EN 61000-4-4
2 kV power cables (Level 3),
2 kV control (Level 4)
* These limits are dependent on the inverter being correctly installed inside a
metallic switchgear enclosure. The limits will not be met if the inverter is not
enclosed.
NOTICE
To achieve these performance levels, you must not exceed the default Pulse
frequency nor use cables longer than 5 m (16.40 ft).
Table 9-4
Compliance Table
Model
Remarks
Case 1 – General Industrial
6SE6410-2U***-**A0
Unfiltered units, all voltages and powers. The product standard EN 61800-3
+ A11 for “Adjustable speed electrical power drive systems – Part3: EMC
product standard including specific test methods” specifies limits for
conducted emissions, which cannot be matched from unfiltered inverters in
the 2
nd
environment.
If compliance with the product standard is required, filtered inverters ( as
described under case 2) have to be installed.
Case 2 – Filtered Industrial
6SE6410-2B***-**A0
All units with integral filters for screened motor cables up to 10 m (32,80 ft)
[Class A]
Содержание micromaster 410
Страница 1: ......
Страница 5: ......
Страница 10: ...Safety Instructions Issue 04 02 MICROMASTER 410 Operating Instructions 10 6SE6400 5EA00 0BP0 ...
Страница 14: ...Table of Contents Issue 04 02 MICROMASTER 410 Operating Instructions 14 6SE6400 5EA00 0BP0 ...
Страница 44: ...3 Commissioning Issue 04 02 MICROMASTER 410 Operating Instructions 44 6SE6400 5EA00 0BP0 ...
Страница 56: ...5 System Parameters Issue 04 02 MICROMASTER 410 Operating Instructions 56 6SE6400 5EA00 0BP0 ...
Страница 62: ...6 Troubleshooting Issue 04 02 MICROMASTER 410 Operating Instructions 62 6SE6400 5EA00 0BP0 ...
Страница 66: ...7 MICROMASTER 410 Specifications Issue 04 02 MICROMASTER 410 Operating Instructions 66 6SE6400 5EA00 0BP0 ...
Страница 68: ...8 Options Issue 04 02 MICROMASTER 410 Operating Instructions 68 6SE6400 5EA00 0BP0 ...
Страница 74: ......
Страница 80: ...Index Issue 04 02 MICROMASTER 410 Operating Instructions 80 6SE6400 5EA00 0BP0 ...
Страница 82: ...MICROMASTER 410 Operating Instructions 82 6SE6400 5EA00 0BP0 ...
Страница 84: ......