6 Troubleshooting
Issue 04/02
MICROMASTER 410 Operating Instructions
58
6SE6400-5EA00-0BP0
6.3 Fault
messages
Fault
Possible Causes
Diagnose & Remedy
Reac-
tion
F0001
OverCurrent
Ø
Motor power (P0307) does not
correspond to the inverter power
(r0206)
Ø
Motor lead short circuit
Ø
Earth
faults
Check the following:
1. Motor power (P0307) must correspond to
inverter power (r0206).
2. Cable length limits must not be exceeded.
3. Motor cable and motor must have no short-
circuits or earth faults
4. Motor parameters must match the motor in
use
5. Motor must not be obstructed or overloaded.
Ø
Increase
the
ramp
time
Ø
Reduce the boost level
OFF2
F0002
OverVoltage
Ø
Overvoltage can be caused either
by too high main supply voltage
or if motor is in regenerative
mode.
Ø
Regenerative mode can be
caused by fast ramp downs or if
the motor is driven from an active
load.
Check the following:
1. Supply voltage (P0210) must lie within limits
indicated on the inverter rating plate.
2. DC-link voltage controller must be enabled
(P1240) and parameterized properly.
3. Ramp-down time (P1121) must match inertia
of load.
NOTE
Higher inertia requires longer ramp times
OFF2
F0003
UnderVoltage
Ø
Main
supply
failed.
Ø
Shock load outside specified
limits.
Check the following:
1. Supply voltage (P0210) must lie within limits
indicated on the inverter rating plate.
2. Supply must not be susceptible to temporary
failures or voltage reductions.
OFF2
F0004
Inverter Over
Temperature
Ø
Ventilation
inadequate
Ø
Ambient temperature is too high.
Check the following:
1. Pulse frequency must be set to default value
2. Ambient temperature could be higher than
specified for the inverter
OFF2
F0005
Inverter I
2
t
Ø
Inverter
overloaded.
Ø
Duty cycle too demanding.
Ø
Motor power (P0307) exceeds
inverter power capability ( r0206).
Check the following:
1. Load duty cycle must lie within specified
limits.
2. Motor power (P0307) must match inverter
power (r0206)
OFF2
F0011
Motor Over
Temperature
I
2
t
Motor overloaded
Check the following:
1. Load duty cycle must be correct
2. Motor temperatur warning level (P0604) must
match.
OFF1
F0041
Stator resistance measurement
failure
Ø
Check if the motor is connected to the
inverter.
Ø
Check that the motor data have been entered
correctly.
OFF2
F0051
Parameter
EEPROM Fault
Read or write failure while saving
non-volatile parameter.
Factory Reset and new parameterization
Change drive
OFF2
F0052
power stack
Fault
Read failure for power stack
information or invalid data.
Change drive
OFF2
Содержание micromaster 410
Страница 1: ......
Страница 5: ......
Страница 10: ...Safety Instructions Issue 04 02 MICROMASTER 410 Operating Instructions 10 6SE6400 5EA00 0BP0 ...
Страница 14: ...Table of Contents Issue 04 02 MICROMASTER 410 Operating Instructions 14 6SE6400 5EA00 0BP0 ...
Страница 44: ...3 Commissioning Issue 04 02 MICROMASTER 410 Operating Instructions 44 6SE6400 5EA00 0BP0 ...
Страница 56: ...5 System Parameters Issue 04 02 MICROMASTER 410 Operating Instructions 56 6SE6400 5EA00 0BP0 ...
Страница 62: ...6 Troubleshooting Issue 04 02 MICROMASTER 410 Operating Instructions 62 6SE6400 5EA00 0BP0 ...
Страница 66: ...7 MICROMASTER 410 Specifications Issue 04 02 MICROMASTER 410 Operating Instructions 66 6SE6400 5EA00 0BP0 ...
Страница 68: ...8 Options Issue 04 02 MICROMASTER 410 Operating Instructions 68 6SE6400 5EA00 0BP0 ...
Страница 74: ......
Страница 80: ...Index Issue 04 02 MICROMASTER 410 Operating Instructions 80 6SE6400 5EA00 0BP0 ...
Страница 82: ...MICROMASTER 410 Operating Instructions 82 6SE6400 5EA00 0BP0 ...
Страница 84: ......