6 Troubleshooting
MICROMASTER 410 Operating Instructions
6SE6400-5EA00-0BP0
57
6 Troubleshooting
WARNING
♦
♦
♦
♦
Repairs on equipment may only be carried out by
Siemens Service
, by repair
centers
authorized by Siemens
or by qualified personnel who are thoroughly
acquainted with all the warnings and operating procedures contained in this
manual.
♦
♦
♦
♦
Any defective parts or components must be replaced using genuine Siemens
authorised parts.
♦
♦
♦
♦
Risk of electric shock. The DC link capacitors remain charged for five minutes
after power has been removed.
It is not permissible to open the equipment
until 5 minutes after the power has been removed.
6.1
Troubleshooting with the Standard Inverter LED
The following is a description of the fault and warning indications given by the LED
on the Standard Inverter:
Ø
Inverter Off/No supply:
No LED lit.
Ø
Power On/Ready:
1000 ms On / 1000 ms Off
Ø
Inverter Running OK:
Steady LED
Ø
General Warning:
500 ms On / 200 ms Off
Ø
Fault Condition:
100 ms On / 100 ms Off
6.2
Troubleshooting with the Operator Panel (OP)
If the display shows a fault or warning code, please refer to Section 6.3.
If the motor fails to start when the ON command has been given:
Ø
Check that P0010 = 0.
Ø
Check that a valid ON signal is present.
Ø
Check that P0700 = 2 (for digital input control) or
P0700 = 1 (for OP control).
Ø
Check that the setpoint is present (0 to 10V on Terminal 7) or the setpoint has
been entered into the correct parameter, depending upon the setpoint source
(P1000). See the Parameter List for further details.
If the motor fails to run after changing the parameters, set P0010 = 30 then P0970
= 1 and press
P
to reset the inverter to the factory default parameter values.
Now use a switch between cobtrol terminals
1
and
4
. The drive should now run to
the defined setpoint by analogue input.
NOTICE
Motor data must relate to the inverter data power range and voltage.
Содержание micromaster 410
Страница 1: ......
Страница 5: ......
Страница 10: ...Safety Instructions Issue 04 02 MICROMASTER 410 Operating Instructions 10 6SE6400 5EA00 0BP0 ...
Страница 14: ...Table of Contents Issue 04 02 MICROMASTER 410 Operating Instructions 14 6SE6400 5EA00 0BP0 ...
Страница 44: ...3 Commissioning Issue 04 02 MICROMASTER 410 Operating Instructions 44 6SE6400 5EA00 0BP0 ...
Страница 56: ...5 System Parameters Issue 04 02 MICROMASTER 410 Operating Instructions 56 6SE6400 5EA00 0BP0 ...
Страница 62: ...6 Troubleshooting Issue 04 02 MICROMASTER 410 Operating Instructions 62 6SE6400 5EA00 0BP0 ...
Страница 66: ...7 MICROMASTER 410 Specifications Issue 04 02 MICROMASTER 410 Operating Instructions 66 6SE6400 5EA00 0BP0 ...
Страница 68: ...8 Options Issue 04 02 MICROMASTER 410 Operating Instructions 68 6SE6400 5EA00 0BP0 ...
Страница 74: ......
Страница 80: ...Index Issue 04 02 MICROMASTER 410 Operating Instructions 80 6SE6400 5EA00 0BP0 ...
Страница 82: ...MICROMASTER 410 Operating Instructions 82 6SE6400 5EA00 0BP0 ...
Страница 84: ......