9/140
Siemens
RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
Definitions / Tools
28 Feb 2009
2 Definitions
/
Tools
2.1
Signals and parameters (presentation)
Inputs, outputs and parameters of an application can be influenced in various ways.
This description of functions applies the following symbols:
The room unit influences parameters shown with this symbol.
Parameters identified in this way are parameterized using ETS3 Professional (EIB tool
software).
The RXB Konnex controllers CANNOT be parameterized with ETS2.
Parameters identified with this symbol are parameterized with the ACS service tool.
Parameters identified with this symbol are parameterized with the HandyTool.
This indicates inputs and outputs which communicate with other KNX devices. They are
communication objects (CO).
Graphical symbol for an S-mode input communication object.
Graphical symbol for an LTE input communication object.
Graphical symbol for an S-mode output communication object.
Graphical symbol for an LTE output communication object.
The communication objects of the RXB Konnex controllers work in part in S-mode, in
part in LTE mode, and in part in both modes. These objects are described accordingly.
The following table describes each communication object working in S-mode:
Schedule Use
(input communication
object)
Flags
R
W
C
T
U
Type
Receive timeout
States
0 1 1 0 0 20.002
DPT_BuildingMode
Yes
0 = In use
1 = Not in use
2 = Protection
(1)
Communication object name.
Flags: R
Read
W Write
C Communication
T Transmit
U Update
Type
Konnex data type.
Send heartbeat
Yes = Cyclical send.
Receive timeout
Yes = Cyclical receive (timeout).
States or values
Range of states or values which can be adopted
by the communication object.
A list of all S-mode communication objects is located in section 12.5; see a detailed
description of the Konnex data types in section 12.10.
Room
unit
ETS3
Professional
STOP
Important!
ACS
Service
HandyTool
KNX
R
CO
S-mode communication
objects
(1)
Key
Note