145/166
Siemens
RXB (KNX) application library
FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05
Building Technologies
KNX information
28 Feb 2009
13.5.2 S-mode output communication objects
Flags:
R
Read
T
Transmit
W
Write
U
Update
C
Communication
1)
C.S. = Company specific
For internal use only
Name
Flags:
Data point type (KONNEX)
Send
See
R W C T U
heartbeat
page
Alarm info
1 0 1 1 0 219.001 DPT_AlarmInfo
yes
Analog input B1
1 0 1 1 0 9.001
DPT_Value_Temp
yes
Common alarm.
1 0 1 1 0 1.005
DPT_Alarm
yes
Cooling coil output
1 0 1 1 0 5.001
DPT_Scaling
yes
Digital input 1
1 0 1 1 0 1.001
DPT_Switch
no
Digital input 2
1 0 1 1 0 1.001
DPT_Switch
no
Effective application mode
1 0 1 1 0 20.105 DPT_HVACContrMode
yes
Effective occupancy
1 0 1 1 0 20.003 DPT_OccMode
yes
Effective room operating mode
1 0 1 1 0 20.102 DPT_HVACMode
yes
Effective room operating mode
Comfort
1 0 1 1 0 1.001
DPT_Switch
yes
Effective room operating mode
Economy
1 0 1 1 0 1.001
DPT_Switch
yes
Effective room operating mode
Precomfort
1 0 1 1 0 1.001
DPT_Switch
yes
Effective room operating mode
Protection
1 0 1 1 0 1.001
DPT_Switch
yes
Effective room temperature
1 0 1 1 0 9.001
DPT_Value_Temp
yes
Effective setpoint
1 0 1 1 0 9.001
DPT_Value_Temp
yes
Effective setpoint cooling
1 0 1 1 0 9.001
DPT_Value_Temp
yes
Effective setpoint heating
1 0 1 1 0 9.001
DPT_Value_Temp
yes
Effective setpoint offset
1 0 1 1 0 9.002
DPT_Value_Tempd
yes
Electrical power
1 0 1 1 0 9.024
DPT_Power
yes
Energy demand room
1 0 1 1 0 6.001
DPT_Percent_V8
yes
Fan output
1 0 1 1 0 5.001
DPT_Scaling
yes
Heating coil output
1 0 1 1 0 5.001
DPT_Scaling
yes
Heating/cooling output
1 0 1 1 0 1.100
DPT_Heat/Cool
yes
Heating outp bus el heating
1 0 1 1 0 5.001
DPT_Scaling
yes
Heating surface output
1 0 1 1 0 5.001
DPT_Scaling
yes
Master/slave HVAC controller
output
1 0 1 1 0 C.S.
1)
13
Byte
yes
Master/Slave room unit output
1 0 1 1 0 C.S.
1)
4
Byte
yes
Outside air damper.
1 0 1 1 0 5.001
DPT_Scaling
yes
Presence detector output
1 0 1 1 0 1.018
DPT_Occupancy
yes
Present setpoint.
1 0 1 1 0 9.001
DPT_Value_Temp
yes
Present setpoint ...
(6 indiv. values)
1 0 1 1 0 9.001
DPT_Value_Temp
yes
Present setpoints cooling
1 0 1 1 0 222.100 DPT_TempRoomSetpSetF16[3] yes
Present setpoints heating
1 0 1 1 0 222.100 DPT_TempRoomSetpSetF16[3] yes
Return air temperature output
1 0 1 1 0 9.001
DPT_Value_Temp
yes
Room temperature output
1 0 1 1 0 9.001
DPT_Value_Temp
yes
Status
1 0 1 1 0 C.S.
1)
2
Byte
no
Supply air temperature output
1 0 1 1 0 9.001
DPT_Value_Temp
yes
Window switch output
1 0 1 1 0 1.019
DPT_Window_Door
yes