Triggering the special functions by the building automation and control system can be
disabled in each room controller via tool.
ETS3 Professional Go to the Functions menu for the disable feature.
HandyTool
See parameters in the last column of the above table.
10.8 Morning boost (Morning Warmup, 2)
This function is used to raise the temperature in a room as quickly as possible to the
Precomfort
heating setpoint at the end of the night setback period.
Objective: Preheat the room in the event of heating.
100
0
TR
10
3
84D
2
3
Y [%]
SpH
Stby
SpC
Stby
The following conditions must be fulfilled:
•
The room controller must be in
Economy
room operating mode.
The function can be disabled in the room controller with ETS3.
The function must be enabled via the building automation and control system
(communication object
Application mode
, see page 105).
The function is disabled via the building automation and control system.
10.9 Precooling (Precool, 5)
This function is used to cool rooms to the
Comfort
cooling setpoint prior to actual
occupancy.
100
TR
10
3
84D
2
5
0
Y [%]
SpH
Cmf
SpC
Cmf
Disable special
functions
Enable function
Start function
Terminate function