45/166
Siemens
RXB (KNX) application library
FNC Description of functions for FC-10, FC-11, FC-12
CM110385en_05
Building Technologies
Room operating modes
28 Feb 2009
Time schedule
Use
Time schedule
Occupancy
Rooms 1 … 3
Window contact
Room 3
Effective room
operating mode
Room 3
Building in use
Building not in use
Building protection
Occupied
Standby
Unoccupied
Window open
Window closed
Comfort
Precomfort
Economy
Protection mode
06:00
22:00
08:00
17:00
13:00
12:00
10385D02
1)
2)
1)
Rooms with a room unit ( /Auto button) or presence detector
The operating mode in Rooms 1 and 2 of a building is determined centrally by the
Use
and
Occupancy
time schedules
.
The
Occupancy
time schedule defines the period
during which both rooms are required to be available
(Standby).
Comfort
mode is then initiated locally via the room unit (Room 1) or presence detector
(Room 2).
The following conditions are specified:
•
Overall, the building is in use from 06.00 to 22.00 (
Building use
time schedule).
•
Rooms 1 and 2 must be available from 08.00 to 18.00
(Occupancy
time schedule:
Standby
)
•
The occupants of Room 1 continue working in the evening beyond the programmed
occupancy period. At the end of the programmed period of occupancy, the room
operating mode changes to
Economy
, even if the room unit is set to Auto (1).
Comfort
mode can now be re-activated with the Auto switch on the room unit (2).
Comfort
remains active for the pre-defined
Temporary Comfort mode
period (see
page 126). However, at the end of the "building-in-use" period the
Temporary
Comfort
period is also overridden and the room operating mode reverts to
Economy
mode (3).
•
In Room 2, in the evening, there are still people in the room beyond the "building-in-
use" period (4). However, at the end of the building-in-use period the room operating
mode still changes to
Economy
mode
.
An alarm can also be tripped, if required.
Example 2