135/140
Siemens
RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
Integration of RXB in DESIGO/Synco
28 Feb 2009
14.4 Case 4: Display in DESIGO/Synco, with
shared Synco schedule
•
Communication:
– Between the controllers: LTE mode via zones.
– With DESIGO:
Individual addressing or S-mode.
– With ACS:
Individual addressing.
•
RXB display:
DESIGO and ACS.
•
Synco display:
DESIGO and ACS.
•
RXB schedule:
from Synco.
•
Energy demand:
to Synco.
•
The DESIGO schedule must be disabled by a specialist.
•
In theory, simultaneous display on DESIGO and Synco is possible. However,
problems occur when manipulating values (heartbeat, “last one wins”).