37/166
Siemens
RXB (KNX) application library
FNC Description of functions for FC-10, FC-11, FC-12
CM110385en_05
Building Technologies
Room operating modes
28 Feb 2009
The state of the room controller (result of the logic OR operation) is mapped to the
building automation and control system via the following S-mode communication object:
Window contact output (Output communication object)
Flags
R W C T U
Type
Send heartbeat
States
1 0 1 1 0 1.019
DPT_WindowDoor
Yes
0 = Closed
1 = Open
Master/slave applications
Bindings are required in S-mode, in order to transmit the slave window contact status to
the master.
5.3.2
Central control of room operating mode via input from
the
Use
time schedule
S
Central
Local
1.
2.
3.
S
DI
S
S
S
DI
S
3.
Controller
Prio
PPS2
3.
S
This time schedule determines the overall period of
time for which the entire building is in use. Typically,
this schedule is used for night setback throughout
the building, or for longer periods when the building
is not in use.
Outside the “building-in-use” times, inputs from
3
rd
priority sources are disabled. This prevents
demand signals from being sent to the primary plant
when, for example, a security guard enters a room.
The table below shows the three possible occupancy states and the resulting e
ffective
room operating mode.
Switch state
Description
Effective room op. mode
Building in use
•
Full availability of all plant
•
Building enabled for use
•
Inputs of priority 3 are enabled (
Occupancy
time
schedule, presence detector, room unit, and
Temporary Comfort mode)
As defined by
Occupancy
time schedule, presence
detector or room unit
Building not in use
•
Reduced availability of plant
•
Inputs of priority 3 are disabled (
Occupancy
time
schedule, presence detector, room unit, and
Temporary Comfort mode)
•
Application:
Building temporarily not in use
The building must reach the
Comfort
temperature within hours
Economy
Building protection
•
Setpoints reduced to the minimum necessary to
protect the building fabric.
•
Inputs of priority 3 are disabled (
Occupancy
time
schedule, presence detector, room unit, and
Temporary Comfort mode)
•
Application:
Longer periods of non-use of the building
Protection mode
KNX
R
CO
Note
Effective
room operating mode