47/52
Siemens
RXB application library (KNX)
FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_0
3
Building Technologies
FNC18 – Two-pipe fan coil (changeover) and radiator
30.11.2007
The following parameters are available with application FNC12.
They are set via ETS, ACS, or HandyTool.
Menu
Parameters.
Values/Range
Basic setting
Communication Communication
mode
S-mode / LTE and S-mode
S-mode.
Receive
timeout
0 ... 105 min.
60 min.
Send
heartbeat
0 ... 105 min.
45 min.
Room temperature setpoints
Protection cooling setpoint
10 ... 40 °C
40 °C
Economy cooling setpoint
10 ... 40 °C
35 °C
Precomfort cooling setpoint
10 ... 40 °C
28 °C
Comfort
cooling
setpoint
10 ... 40 °C
24 °C
Comfort
heating
setpoint
10 ... 40 °C
21 °C
Precomfort heating setpoint
10 ... 40 °C
19 °C
Economy heating setpoint
10 ... 40 °C
15 °C
Protection heating setpoint
10 ... 40 °C
12 °C
Other setpoints
Downdraft compensation
Outside temp 0% valve pos
Outside temp max valve pos
Maximum valve pos
–30 ... 10°C
–30 ... 10°C
0 ... 100%
0°C
–10°C
100%
Sequences Control
sequence
– Heating only
– Cooling only
– Changeover
Cooling only
Actuator type heating/cooling coil valve
– STA71
– SSA81
– STA72E
– SSB81
– STE71
– SSP81
– STE72
– SQS81
– STP71
– STP72E
– Motorized 3rd devices
– Thermal 3
rd
devices
– Motorized bus
STP72E
Actuator type heating surface valve
– STA71
– SSA81
– STA72E
– SSB81
– STE71
– SSP81
– STP71
– SQS81
– STP72E
– Motorized 3rd devices
– Thermal 3
rd
devices
– Motorized bus
STA72E
Motorized and electromechanic Runtime
0 ... 360 s
150 s
Motorized Offset
0 ... 360 s
0 s
LTE mode Heating coil outp bus valve
Off/On Off
Cooling coil outp bus valve
Off/On Off
Heating surface outp bus valve
Off/On Off
Fan control.
Fan speeds
– External control
– 1-speed/2-speed/3-speed
3-speed
Fan
control.
Manual / Auto
Auto
Minimum on time.
1 ... 10 min
6 min
Temperature sensor B1
– Room
– Return air
– Measured value only
– No sensor
No sensor
Periodic fan kick Comfort
0 ... 90 min (90min = Off)
90 min (Off)
Periodic fan kick Economy
0 ... 360 min (360min = Off)
360 min (Off)
Room unit
Measured value correction
– 3 ... 3 K
0 K
Setpoint offset range
± 0 ... 10 K
± 3 K
Local
Comfort
mode
Enabled / Disabled
Enabled
Room
unit
Without LCD / with LCD
Without LCD
With LCD Display heating/cooling symbols
Enabled / Disabled
Enabled
Temperature
unit
°C or °F
°C
Standard
display
No display / Room
temperature / Setpoint
Room temperature.
Setpoint
display
Absolute / Relative
Relative
Configuration