111/140
Siemens
RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
General / central functions
28 Feb 2009
10.15 Free inputs/outputs
In a building automation and control system, the free I/Os can be used to e.g. query
switching states or for direct switch control of another device over the network.
However, these functions are not suitable for time-critical processes (<1 s).
Free inputs can be defined as NC or NO (see 10.2).
If not already in use, the following inputs and outputs can be used freely:
RXB24.1/CC-02 Appli-
cation
Digital inputs
Triac outputs
D1
D2
Y1
Y2
Y3
Y4
CLC01
1 2
•
•
z
z
CLC02
3 4
•
•
•
•
RAD01
5 6
•
•
z
z
Digital inputs
7
If "Not used" (see page 102), can be used freely.
Triac outputs
X Used by the application.
z
Can be used freely.
•
Only freely usable with bus valve actuators.
(All combinations: see CM110671).
Parameter setting for free inputs see 10.2, page 102.
10.15.1 Digital inputs on the KNX bus
D1
D2
RXB... Room controller
Digital input 1
Digital input 2
10385Z19en
The following S-mode input and output communication objects are used when taking
advantage of spare inputs and outputs:
Digital input 1 (output communication object)
Digital input 2 (output communication object)
Flags
R W C T U
Type Send
heartbeat States
1 0 1 1 0
1.001
DPT_Switch
No
Parameter setting in tool
Cause: digital input
Effect: bus output
Free: Bus = 1 = Contact closed
Contact closed
1
Contact
open
0
Free: Bus = 1 = Contact open
Contact open
1
Contact
closed
0
Key
KNX
R
CO