82/140
Siemens
RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
Control sequences
28 Feb 2009
Select
Sequences
. After selecting third-party devices, a new window opens in which
the heating runtime can be set.
Select the actuator runtime from the
Sequences
menu:
HandyTool
See the parameters in the last column of the following table.
Parameter Basic
setting
Range
Resolution
HandyTool
Running time heat surf valve
150 s
0 ... 360 s
1 s
*064
Offset heating surface valve
0 s
0 ... 360 s
1 s
*066
ETS3
Professional
ACS