120/166
Siemens
RXB (KNX) application library
FNC Description of functions for FC-10, FC-11, FC-12
CM110385en_05
Building Technologies
Master/slave
28 Feb 2009
10.2 LTE mode with zones
The master/slave configuration is also possible in LTE mode. However, you do not
need to create the individual bindings, but instead define the master/slave zone.
Here too, the following applies: The slaves must be controlled by only
one
master, and
master/slave bindings are only possible between controllers with the same version
(ASN) featuring the same applications and settings.
Select
Master / Slave:
M
S
S
Room 321
322
323
Geogr. zone
5.1.1
5.2.1
5.3.1
Master / Slave
Master
Slave
Slave
M/S zone
5.1.1
5.1.1
5.1.1
Geogr. zone und M/S zones need not be the same. However, every day work is easier
because you see directly to which master a slave belongs.
Select
Master/Slave:
ETS3
Professional
Example
Note
ACS
Service