213/248
Building Technologies Division
Basic documentation LMV36...
CC1P7544en
Infrastructure & Citiies Sector
28 Parameter level
25.09.2013
ESC
P
V
h min s
%
B
ild
156
/0
70
7
The warm settings for fuel-air ratio control of the LMV36... have now been configured.
28.11.12 Cold settings for multistage mode («Lo 2-stage» and «Lo 3-stage»)
Note
Refer to chapters
Warm settings for «Lo 2-stage» and «Lo 3-stage»
!
But with no flame, no actuator travel and no automatic operation after the settings
have been made.
28.11.13 Intensity of flame during curve settings
When setting the curve and the curvepoint is displayed, you can press
/reset
to show the intensity of flame.
When pressing the button for >1 s, a change to parameter 954 is made; when releasing the button, you
return to the curvepoint.
P
V
h min s
%
B
ild 123
/0
707
Example: Curvepoint
Low-flame position
P1.
/reset
>1 s
Change to parameter
954
Parameter
954:
flashes.
The intensity of flame in % is shown on the right.
Example:
954: 0.0
/reset
P
V
h min s
%
B
ild 123
/0
707
Release
/reset
to return to curvepoint
Low-fire
position
P1.