
102/248
Building Technologies Division
Basic documentation LMV36...
CC1P7544en
Infrastructure & Citiies Sector
9 Selection of operating mode
25.09.2013
O
p
era
ti
n
g
mode
pa
ra
me
ter
2
0
1
/
301
Fue
l tra
in
Fue
l-
ai
r ra
tio
co
nt
ro
l
Fue
l ac
tua
to
r
Ai
r a
c
tu
at
or
Fe
ed
ba
ck
s
ig
n
al
VSD
Description
26
HO o. Umsp
2-stage
¹)
2-stage
●
●
Heavy oil direct ignition without circulation control, electronic 2-stage
ratio control. Optional with VSD with speed feedback signal
27
HO o. Umsp
3-stage
¹)
3-stage
●
●
Heavy oil direct ignition without circulation control, electronic 3-stage
ratio control. Optional with VSD with speed feedback signal
(Also refer to chapter
Fuel trains
)
¹) Selected operating mode is not released for the basic unit.
With select: Error code 210 diagnostic code 0
The VSD can be used with any of the operating modes (refer to chapter
VSD
).
No. Parameter
542
Activation of VSD / PWM fan
0 = inactive
1 = active
Note
For configuration of the analog output when the VSD is activated, refer to
chapter
Load output X74 pin 3
!
9.1 Deleting
curves
To delete curves, the operating mode must be set to undefined «--». In that case, only
the fuel curves are deleted, the direction of rotation or the reference position of the
actuators is not changed.