
118/248
Building Technologies Division
Basic documentation LMV36...
CC1P7544en
Infrastructure & Citiies Sector
11 Electronic fuel-air ratio control
25.09.2013
11.4.6 Limitation of modulation range
If the modulation range for stage 1 and stage 2, or stage 3, shall be further restricted, 4
parameters can be used to define a new low-fire and high-fire position.
No. Parameter
545
Lower output limit
undefined = 20 %
565
Fuel 1: Lower output limit
undefined = 20 %
546
Upper output limit
undefined = 100 %
566
Fuel 1: Upper output limit
undefined = 100 %
11.5 End of operating position
When there is no more heat request, the system switches to phase 62. Here, the burner
runs down to low-fire as long as possible before the valves are shut.
The available period of time can be set via parameter 212. If this time is set to the
minimum value, the burner is immediately shut down if there is no more request for
heat. If the time exceeds 32 seconds, the burner always runs to low-fire. Naturally, it is
also possible to set intermediate times.
No. Parameter
212
Max. time down to low-fire