
201/248
Building Technologies Division
Basic documentation LMV36...
CC1P7544en
Infrastructure & Citiies Sector
28 Parameter level
25.09.2013
)
Air
Figure 99: Setting the curvepoints
Note
Curvepoints
P2
to
P8
are automatically computed as a straight line between
P1
and
P9
.
Example 1 = gas modulating
P0
,
P1
and
P9
are set as described:
Curvepoint
Value
1
fuel
Value 2
air
P0
30.0 22.0
P1
32.0 24.0
P9
80.0 90.0
P2
through
P8
have automatically been
calculated:
Curvepoint Value
1
fuel
Value 2
air
P2
38.0 32.3
P3
44.0 40.5
P4
50.0 48.8
P5
56.0
57
P6
62.0 65.3
P7
68.0 73.5
P8
74.0
81.8