
135/248
Building Technologies Division
Basic documentation LMV36...
CC1P7544en
Infrastructure & Citiies Sector
13 Fan control
25.09.2013
13.8 Speed control
The LMV36... controls the fan motor’s speed to the setpoint. To ensure that the speed
can still be increased when the maximum speed is reached, the speed is standardized
when the motor is controlled at 95%. Hence, with a speed setpoint of 100%, a speed
increase of 5% is still possible.
The control range of the LMV36... is +15% / -10%. If this range is not sufficient, error 80
or 83 can occur.
Error
code
Diagnostic code Meaning for the LMV36... system
80
1
Control range limitation at the bottom
2
Control range limitation at the top
Note
Internal control with a VSD or PWM fan motor must not be activated. Otherwise,
speed variations can occur, resulting from simultaneous control actions from both the
basic unit and internal control.